Delta Electronics VFD-E Serie Manual Del Usuario página 30

Tabla de contenido
Figura 1 para los modelos de la Serie VFD-E
VFD002E11A/21A, VFD004E11A/21A, VFD007E21A, VFD002E11C/21C, VFD004E11C/21C,
VFD007E21C, VFD002E11P/21P, VFD004E11P/21P, VFD007E21P
Fuse/NFB(None Fuse Breaker)
R(L1)
S(L2)
Recommended Circuit
when power supply
is turned OFF by a
fault output
Factory setting:
NPN Mode
NPN
Factory
Sw1
setting
PNP
Please refer to Figure 7
for wiring of NPN
mode and PNP
mode.
Factory setting:
ACI Mode
AVI
Sw2
ACI
ACI/AVI switch
When switching to AVI,
it indicates AVI2
Main circuit (power) terminals
Revisión Noviembre 2007, 03EE, SW--PW V1.10/CTL V2.10
SA
MC
ON
OFF
MC
FWD/Stop
REV/Stop
Multi-step 1
Multi-step 2
Multi-step 3
Multi-step 4
Digital Signal Common
3
5K
2
1
Analog Signal Common
Capítulo 2 Instalación y cableado|
braking resistor
BR
(optional)
BUE
braking unit
(optional)
-
R(L1)
U(T1)
S(L2)
V(T2)
W(T3)
E
E
RB
RA
RC
RB
RC
+24V
MO1
MI1
MI2
MI3
MI4
MCM
MI5
MI6
AFM
DCM
E
ACM
+10V
Power supply
+10V 20mA
AVI
Master Frequency
0 to 10V 47K
ACI
4-20mA/0-10V
ACM
8 1
E
Control circuit terminals
Motor
IM
3~
Multi-function contact output
240Vac 2.5A Max.
120Vac 5A Max.
28Vdc 5AMax.
Factory setting is
malfunction indication
Factory setting:
Drive is in operation
48V50mA Max.
Multi-function
Photocoulper Output
Analog Multi-function Output
Terminal
factory setting: Analog freq.
/ current meter
Analog Signal common
E
Factory setting: output frequency
RS-485 serial interface
(NOT for VFD*E*C models)
1: Reserved
2: EV
3: GND
4: SG-
5: SG+
6: Reserved
7: Reserved
8: Reserved
For VFD*E*C models,
please refer to figure 8.
Shielded leads & Cable
0~10VDC/2mA
2-3