LEROY-SOMER
Variable speed motors and geared motors
COMMISSIONING THE PEGASE VMA 10 PC PARAMETER-SETTING SOFTWARE
3.3.3 - Detail of the 3rd window (access to parameters)
Parameter modifications must be made whilst the VARMECA 10 is powered up,
3.4 - The VARMECA 10 parameters
Description of parameters which can be accessed from the PC.
Display
maximum operating frequency
F max
(according to mini DIP K2 position)
F min
minimum operating frequency
ACCEL
acceleration ramp value to pass from 0 to 50 Hz
DECEL
deceleration ramp value to pass from 50 to 0 Hz
U
mot
voltage applied to the motor at base frequency
n
(percentage of mains voltage: base 400 V)
(1)
F
mot
n
base frequency of motor
(1)
BOOST
value of voltage applied in low frequencies
(1)
(percentage of mains voltage)
OVERBOOST
value of voltage applied during starting phase
(1)
(percentage of mains voltage)
PARAMETER-SETTING MANUAL
VARMECA 10
but in the "stop" position (run command disabled)
Description
(1) : the voltage/frequency ratio is illustrated at the end of the table
Ref. 3264 - 4.33/b -1.00
Confirm
parameter
modifications
Return to
previous
window
Exit the
current
window
Adjustment range in
Factory setting
increments of 1
32 to 220 Hz
50 or 80 Hz
6 to 30 Hz
0 to 20 s
0 to 20 s
0 to 100 %
50 to 150 Hz
adapted to the
0 to 40 %
motor according to
the power
adapted to the
0 to 100 %
motor according to
the power
12 Hz
3 s
3 s
100 %
50 Hz
43