2.3 - Read mode

- Connect the console to the VARMECA 20 RS 232 socket.
- Power up the VARMECA 20.
- On power-up, the console display is positioned on the 1st
parameter P01 F-MIN.
The 1st line of the display indicates the parameter
description.
The 2nd line indicates the parameter value and its unit of
measurement.
The
key scrolls through the parameters.
The
key is used for scrolling in the opposite direction.

2.5 - VARMECA 20 parameters

List and description of the parameters which can be accessed by the CDC-VMA 20 console
Display
P01 F-MIN
Minimum operating frequency
P02 REF 0V/4mA
Calibration of the 0V or 4mA min. reference
P03 F-MAX
Maximum operating frequency
P04 REF 10V/20mA
Calibration of the 10V or 20mA max. reference
Acceleration ramp
Ramp value to switch from 0 to 50Hz
*
P05 ACCEL RAMP
Incrementation
In the standard configuration, terminals 9 and
10 must be connected together in order to
modify the value of the acceleration ramp.
Deceleration ramp
Ramp value to switch from 50 to 0Hz
*
Incrementation
P06 DECEL RAMP
In the standard configuration, terminals 9 and
10 must be connected together in order to
modify the value of the deceleration ramp.
Stop mode
*
Freewheel = freewheel stop
P07 STOP MODE
ramp = stop following ramp
automatic = controlled deceleration
Voltage applied to the motor at frequency
P08 UN-MOT
base
P09 FN-MOT
Base frequency of motor
Selection of voltage/frequency ratio
constant = fixed U/F
Voltage P08 will be applied at the point of
*
frequency P09
P10 CONTROL U/F
dynamic = dynamic U/F
The voltage adapts automatically to the
motor load (position of mini dip switch
K3 = OFF)
*
This parameter can be modified if the VARMECA is powered up and a stop command has been issued.
50
PARAMETER SETTING MANUAL
VARMECA 20
Variable speed motors and geared motors
COMMISSIONING THE CDC-VMA 20 CONSOLE
Description
2.4 - Parameter setting mode
• Parameter modifications must be made with the
VARMECA 20 stopped (run command disabled).
To modify a setting, use the
parameter.
The
key is used to make the parameter to be modified
flash.
Modify the setting value with the
As soon as the value differs from the value memorised, the
message M ? appears.
When the desired setting value has been reached, it can be
memorised using the
key.
MEM.
M ? disappears from the display.
The
key is used to quit parameter-setting mode.
Adjustment range
VMA A20
6 to Fmax
0 to Fmax
32 to 220Hz
32 to 100Hz
32 to 220Hz
32 to 100Hz
0 to 100s
1s
0 to 100s
1s
ramp, freewheel or
ramp or freewheel
automatic
0 to 480V
50 to Fmax
constant or dynamic
3532 - 05.2004 / f
or
keys to access the
or
keys.
Factory setting
VMA B20
12Hz
12Hz
50 or 80Hz
50 or 80Hz
0 to 40s
3s
0.1s
0 to 40s
3s
0.1s
ramp
230 or 400V
50Hz
constant from
0.25 to 1.1Kw
dynamic from
1.5 to 4Kw