1.4.6 - Standard configuration: regulation with the integrated PI loop - PI reference using the local
button or external reference - 2 operating directions
MAINS
SUPPLY
Terminals
+10 V analogue source
1
rated current: 3 mA
Analogue input
2
PI reference
Analogue input - PI sensor feedback
3
0 to +10 V - Impedance = 100 kΩ
4
0 V - common with terminal 6
Logic input S1
5
PI reference selection
6
0 V - common with terminal 4
Logic input
7
run reverse/stop
Logic input
8
run forward/stop
Relay output 250 V - 1A
9 - 10
36
PARAMETER-SETTING MANUAL
VARMECA 10
Variable speed motors and geared motors
GENERAL INFORMATION
L1
L2
L3
PE
9
Fault
relay
10
Specifications
Switched off or faulty
On
+10V
1
PI reference (local button
2
or external reference)
3
PI sensor feedback (0-10V)
4
0V
S1
PI reference selection (local
5
button or external reference)
6
0V
7
Run reverse / stop
8
Run forward / stop
Associated parameter setting
CDC-VMA
Terminal block configuration
P14 = 0
Terminal N˚3 assignment
P20 = 1
PI reference selection
Reference
Local button
Ext. ref. 0 - 10 V
Ext. ref. 4 - 20 mA
Setting other parameters
see sections 2 and 3
Ref. 3264 - 4.33/b -1.00
PEGASE VMA 10
STANDARD
PI input
switches
S1
K1
K4
1
-
ON
0
ON
ON
0
OFF
ON