Kenmore 79075353314 Instrucciones De Instalación página 9

Idiomas disponibles

Idiomas disponibles

3 & 4-Wire permanent connections ONLY
IMPORTANT:
3 - Wire permanent connection - follow
Steps 1, 2 and 5 below.
IMPORTANT:
4 - Wire permanent connection - follow
Steps 1 thru 5 below.
Before wiring the range, review the suggested power
source location drawings in Fig. Aand B on page 4. If
connecting to a 4-Wire electrical system (new branch-
circuit or mobile home requires 4-Wire connection):
1.
3 and 4- Wire Permanent Connections - Follow the
manufacturer's installation instructions supplied with
the strain relief and install (See Figre 28).
2.
3 and 4 - Wire Permanent Connections - Strip
insulation away from the ends of the permanent wiring
for Line 1, Line 2, Neutral (also strip ground wire on
4-Wire Connections). Tighten all 3 wire leads to the
terminal block (follow wire locations shown in Fig. 31).
FOR 3 & 4-Wire Permanent Connections
Terminal
Tighten all 3
block
wire leads
Ground plate
Ground screw
Ground strap
Fig. 31
NOTE:
Non-terminated field wire compression
connections must be set at approximately 22in./lbs.
Always use 10 ga. wire or larger.
IMPORTANT NOTE:
DO NOT LOOSEN the factory
installed nut connections which secure the range
wiring to the terminal block. Electrical failure or loss
of electrical connection may occur if these 3 nuts are
loosened or removed.
NOTE:
For 3-Wire Permanent Connections skip Steps
3 and 4 and continue with Step 5.
3.
4-Wire Permanent Connection ONLY - Disconnect
the ground strap. Remove the factory installed ground
screw & plate to release the factory installed copper
ground strap from frame of the appliance. Cut and
discard the copper strap from the terminal block. KEEP
the ground screw, ground plate and go to Step 4.
PROPER
GROUND
@—
PLATE —>
r
G
, °
-
GROUND FOR
4-WIRE
x
PERMANENT
GROUND
CONNECTION
GROUND
WIRE LEAD
SCREW
Fig. 32
4.
4-Wire Permanent Connection ONLY - Connect the
ground wire lead (Green) to the frame of the appliance
using the ground screw & plate as shown in Fig. 32.
Be sure to install using the same hole in the frame
where the ground screw was originally installed.
5.
3 and 4 - Wire Permanent Connections - Make sure
all connections are tightened securely and replace the
rear access cover (See Fig. 25).
Provide an adequate gas supply.
This range is pre-set to operate on 4" natural gas manifold
pressure. The Pressure Regulator is connected to the
manifold and MUST be connected in series with the gas
supply line (See Fig. 33 on page 10).
Care must be taken during installation of range not to
obstruct the flow of combustion and ventilation air. The gas
supply line should be 1/2" or 3/4" LD.
For proper operation, the maximum inlet pressure to the
regulator should be no more than 14 inches of water
column pressure. The inlet pressure to the regulator must
be at least 1 inch greater than regulator manifold pressure.
Examples: If regulator is set for natural gas 4 inch manifold
pressure, inlet pressure must be at least 5 inches;
if regulator has been converted for LP/Propane gas
10 inch manifold pressure, inlet pressure must be at least
11 inches. Leak testing of the appliance shall be conducted
according to the instructions in Step E.
loading