8.1.5 Boost mode setting
1. Select "Boost mode setting" in
the "Service settings" menu.
Device settings
SERVICE SETTINGS
Information
User modes settings
Fans settings
Heaters settings
Filter settings
Frost protection settings
Boost mode settings
Modbus settings
8.1.6 Frost protection setting
1. Select "Frost protection
setting" in the "Service
settings" menu.
Device settings
SERVICE SETTINGS
Information
User modes settings
Fans settings
Heaters settings
Filter settings
Frost protection settings
Boost mode settings
Modbus settings
2. Set "Normally open" or
"Normally closed" by clicking
on the pencil symbol next to
"Logic status IN1".
Boost mode settings
Service settings > Boost mode settings
Boost mode IN1 Logic state
Normally Open
Supply fan control from IN1
100%
Extraction fan control from IN1
100%
2. To enable or disable pre-
heater operation, set "Yes"
or "No" next to "Pre-heater
enabled".
Frost protection settings
Service settings > Frost protection settings
Frost protection enabled
On
Initial fan settings
Work modes
Pre-heater enabled
Yes
Frost protection activation temperature
3°C
Frost protection disactivation hysteresis
3°C
Supply fan speed change
Yes
Minimum supply fan control
30%
ENGLISH
Boost mode IN1 Logic state
NORMALLY OPEN
NORMALLY CLOSED
Confirm
3. To enable or disable flow
unbalance, set "Yes" or "No"
next to "Supply fan speed
change".
Frost protection settings
Service settings > Frost protection settings
Frost protection enabled
On
Initial fan settings
Work modes
Pre-heater enabled
Yes
Frost protection activation temperature
3°C
Frost protection disactivation hysteresis
3°C
Supply fan speed change
Yes
Minimum supply fan control
30%
47
loading