• Power cables must be the ordinary polyvinyl chloride sheathed type, designation 60227 IEC53 (RVV), and comply with
standards GB/T 5023.5-2008/IEC 60227-5:2003.
• The three power supply cable conductors must have a nominal cross-section of no less than 0.75 mm
core connected to the earthing terminal of the appliance.
• To connect the remote HMI/Modbus master unit to the machine, use cables with a cross-section of between 0.35 mm
and 2.5 mm
. Maximum length 12 m. Given that the display connection cable should be kept separate or away from the
2
power cables, the use of shielded cables is advisable if electromagnetic interference problems are encountered from
other devices installed in the room (causing malfunctioning of the display).
• Use cables with a minimum cross-section of 0.5 mm
7.1
Remote control panel installation and connection
The control panel is wall-mountable (fig. 11). Screws and dowels are not included in the supply.
11
Wall installation
Dimensions
80 mm
for connecting the pre-heater.
2
and a yellow-green
2
Mounting frame
Clamps
ENGLISH
2
43