9.4.2 Service settings (corresponds to installer menu on the Cloud)
In addition to the settings already described in "8.1 Configuration via VORTICE MVHR (via Bluetooth)", via the "Service
settings" menu (password: 1111), it is possible to select:
A) "Information" to view all appliance settings.
B) "Fan settings" to adjust the fan speed in percentages (both supply and extraction) and their possible stop delay. In this
menu there is also the item "Minimum outside temperature" with a corresponding sub-menu for setting the operating
threshold values.
C) "Heater settings" item to set the minimum flow rate (in percentage) of supply air on the duct where the pre-heater is
installed. The value can be set between 20% and 100%.
D) "Modbus setting" item (refer to paragraph "11 Modbus" on page 68 for the modbus values that can be set).
Device settings
SERVICE SETTINGS
A
Information
User modes settings
B
Fans settings
C
Heaters settings
Filter settings
Frost protection settings
Boost mode settings
D
Modbus settings
Alarm control panel
User settings > Alarm control panel
Alarm control panel enable
Yes
Input logic state
Normally closed
Ventilation unit response
Switching off the panel
50%
Extraction fan control
Supply fan control
50%
Airing
Inactive
Airing
A
Information
Service settings > Information
Current work status
Current work mode
Temperatures
Fans control
Filters
Filters - informations
Pre-heater / secondary heater
Actuators
Air quality switch
Operation hours
B
Fans settings
Service settings > Fans settings
Minimum supply fan control
25%
Maximum supply fan control
100%
Minimum extraction fan control
25%
Maximum extraction fan control
100%
Supply fan stop delay
1 min.
Extraction fan stop delay
1 min.
Minimum outdoor temperature
ENGLISH
Minimum outdoot temperature
Fans settings > Minimum outdoor temperature
Outside temperature permit
No
Minimum outdoor temperature
-7°C
Minimum outdoor temperature histeresis
2°C
61