Hold the test magnet (accessory) against
the circle symbol with the label "TEST" on
the instrument housing
Abb. 14: Simulation of the output signal
The test magnet changes the current switching
condition of the instrument. You can check the
change on the signal lamp. Please note that
all connected device are activated during the
simulation.
Caution:
It is absolutely necessary that you remo-
ve the test magnet from the instrument
housing after the simulation.
5.3
Function table
The following table provides an overview of
the switching conditions depending on the set
mode and the level.
Level
Swit-
ching
status
Mode
closed
max.
Mode
open
max.
Mode
closed
min.
LFV200 • IO-Link
Control
Con-
Con-
lamp
trol
trol
lamp
lamp
Yellow
- co-
Green
Red -
verage
- vol-
Fault
tage
signal
indica-
tion
Level
Swit-
ching
status
Mode
open
min.
Fault
any
open
6
Maintenance
6.1
Maintenance
Maintenance
If the device is used properly, no special mainte-
nance is required in normal operation.
Cleaning
The cleaning helps that the type label and mar-
kings on the instrument are visible.
Take note of the following:
•
Use only cleaning agents which do not cor-
rode the housings, type label and seals
•
Use only cleaning methods corresponding
to the housing protection rating
6.2
Rectify faults
Observe the signal lamp. Often the reason for
the fault can be detected.
Error
Cause
Green sig-
Voltage
nal lamp off
supply inter-
rupted.
Electronics
defective
Red signal
Error with
lamp lights
the elec-
(switching
trical
output high-
connection
impedance)
Shortcircuit
or overload
6 Maintenance
Control
Con-
Con-
lamp
trol
trol
lamp
lamp
Yellow
- co-
Green
Red -
verage
- vol-
Fault
tage
signal
indica-
tion
any
Rectification
Check the voltage supply
and the cable connection
Exchange the instrument
or send it in for repair
Connect the instrument
according to the wiring
plan
Check the electrical con-
nection
15