Pressing
Press
to flash.
(SELECT/EXIT)
Press
Press
NOTE: The selected values remain in memory even when the unit is disconnected.
Temporary unlocking of keys
Press
during 3 seconds. An indication appears on the display, the keyboard is unlocked
Approximately 1 minute after the last actuation of any key, the keyboard gets relocked.
Managing the automatic key lock
- To deactivate the automatic keylock, choose "is deactivated" in the Keylock Menu.
- To activate the automatic keylock, choose "is deactivated" in the Service Menu then choose"is activated" in the Keylock Menu.
6.1.2 LED reporting
Green LED steady: pump running
Red LED steady: fault reported
6.1.3 Indications on the display
Normal operation
During operation of the control box:
Example 1:
level :
12 cm
level :
P1 auto
P2 auto
12 cm
level :
12 cm
P1 auto
P2 auto
P1 auto
P2 auto
Example 2:
SW123–HW=0 0 0 0
SW123–HW=0 0 0 0
P1 stop
P2 auto
SW123–HW=0 0 0 0
P1 stop
P2 auto
P1 stop
P2 auto
Alarm display
total pump hours
total pump hours
P1/P2
0025/0028
When an alarm occurs, the current alarm type is displayed (see 6.2.3 Warnings and alarme messages). The pump's LED turns red.
total pump hours
P1/P2
0025/0028
P1/P2
0025/0028
Parameters settings
level :
12 cm
When viewing the menus, the screen displays:
P1 auto
P2 auto
Therm. fault P1
Therm. fault P1
is deactivated
Therm. fault P1
is deactivated
is deactivated
SW123–HW=0 0 0 0
P1 stop
P2 auto
Information retrieval
total pump hours
P1/P2
0025/0028
6.2 MENUS
Therm. fault P1
6.2.1 Parameter settings
is deactivated
The selection of a parameter and the modification of its value are possible with
The following table shows and explains the possible settings.
NOTE
For safety reasons, setting some parameters is only possible if the pump has been stopped manually (pressing
1st LINE ON DISPLAY
base load OFF
base load ON
peak load OFF
peak load ON
High water
(HW)
allows access to the parameter setting and viewing menus.
to enter the selected menu. Press
to select a value.
one last time: the value stops flashing, indicating that it is permanent.
- the upper line on the display indicates the water level measured by the pressure sensor (ex. 1) or the
switching status of the float switches (ex. 2 with SW1: OFF float, SW2: ON float pump 1, SW3: ON float pump
2, HW: Alarm float, P1: Pump 1, P2: Pump 2, O: activated , 1: deactivated)
- the lower line indicates the operating status of the pumps P1 and P2: Hand (the pump has been switched
on manually), Stop (the pump has been switched off manually) or Auto (the pump is switched on or off
depending on the level measurement).
If the pump is running, the motor current and operating status are displayed alternately.
- on the upper line, the parameter,
- on the lower line the selected value for the parameter.
The values can be changed by pressing
Values such as "maintenance interval", "total pump run time", "number of pump starts" can be displayed and
reset (see 6.2.2 Information retrieval).
The alarm log can also be viewed. It stores and displays the last 32 alarms. After this number, the backup
automatically deletes the oldest alert.
2nd LINE ON DISPLAY
(SET VALUE)
XX cm
Choose the values such as
OFF level ≤ OFF level 2nd pump
and
ON level < ON level 2nd pump
1-100 cm
Choose the value such as:
ON level 2nd pump < HW level
and
HW level ≤ max value of level
sensor
to enter the setting value modification: the value starts
and
and
Pump stop level (OFF Level).
NOTE: Modification possible only if the pumps have been stopped
manually (pressing
)
Pump activation level (ON Level).
NOTE: Modification possible only if the pumps have been stopped
manually (pressing
)
Stop level 2nd pump (OFF Level 2nd pump).
NOTE: Modification possible only if the pumps have been stopped
manually (pressing
)
Activation level 2nd pump (ON Level 2nd pump).
NOTE: Modification possible only if the pumps have been stopped
manually (pressing
)
Alarm level.
NOTE: Modification possible only if the pumps have been stopped
manually(pressing
).
21
as described in 6.1.1 Keys.
(see 6.1.1 Keys).
).
SIGNIFICATION