3. Installing the indoor unit
E
D
A
D
left
left rear
left bottom
■ PKFY-WL04/06/08NLMU
C
D
E
en
4
D
D
C
B
D
F
: Points to be fastened (5 points)
: Points to be fastened only when
using the lower hook (2 points)
Fig. 3-5
Fig. 3-6
■ PKFY-WL12/15NLMU
C
B
D
A
E
Fig. 3-7
1 )
2 )
A
Fig. 3-8
3.2.3. Installing the wall mounting fixture
► Since the indoor unit weighs near 13 kg, 29 lbs, selection of the mounting
location requires thorough consideration. If the wall does not seem to be
strong enough, reinforce it with boards or beams before installation.
► The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold
arrow.)
Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
Caution:
• The unit body must be mounted horizontally.
• Fasten at the holes as shown by the arrows.
(Fig. 3-5)
■ PKFY-WL04/06/08NLMU-E
A Min. 124 mm, 4-7/8 inch (674 mm, 26-17/32 inch, or greater with optional drain pump
installation)
B Min. 224 mm, 8-13/16 inch
C Min. 75 mm, 2-61/64 inch (Use the hook positioned on the lower part of the mount board
when the dimension is less than 100 mm, 3-15/16 inch with left, rear left, or lower left
piping, and optional drain pump installation. Refer to 3.4. for details.)
D Fixing screws (4 × 25) 2 in Fig. 3-1
E Level
F Mount board 1
■ PKFY-WL12/15NLMU-E
A Min. 119 mm, 4-11/16 inch (669 mm, 26-11/32 inch or greater with optional drain pump
installation)
B Min. 224 mm, 8-13/16 inch
C Min. 75 mm, 2-61/64 inch (Use the hook positioned on the lower part of the mount board
when the dimension is less than 100 mm, 3-15/16 inch with left, rear left, or lower left
piping, and optional drain pump installation. Refer to 3.4. for details.)
D Fixing screws (4 × 25) 2 in Fig. 3-1
E Level
F Mount board 1 in Fig. 3-1
3.3. Preparing the indoor unit
Caution:
right
The indoor unit cannot be installed with left and right piping
* Check beforehand because the preparatory work will differ depending on the
exiting direction of the piping.
3.3.1. Extraction and processing of the piping (Fig. 3-7)
1. Connection of indoor/outdoor wiring → See page 15.
2. Wrap the felt tape 3 in the range of the refrigerant piping and drain hose which
will be housed within the piping space of the indoor unit.
• Wrap the felt tape 3 securely from the base for each of the refrigerant piping
and the drain hose.
• Overlap the felt tape 3 at one-half of the tape width.
• Fasten the end portion of the wrapping with vinyl tape.
A Water pipe (IN)
B Water pipe (OUT)
C Indoor connection cable
D Drain hose
E Felt tape 3 in Fig. 3-1
3. Be careful that the drain hose is not raised, and that contact is not made with the
indoor unit box body.
Do not pull the drain hose forcefully because it might come out.
B
3.3.2. Right rear and right bottom piping (For WL04/06/08 model)
(Fig. 3-8)
A
Caution:
Do not bend two pipes at the same time when install right bottom piping.
1) Be careful that the drain hose is not raised, and is not contacted with the
indoor unit box body.
Arrange the drain hose at the underside of the piping and wrap it with felt
tape 3.
2) Securely wrap the felt tape 3 starting from the base. (Overlap the felt tape at
one-half of the tape width.)
A Cut off for right bottom piping.