H Circuit CONT or OPEN
The ------ indication is for CONT (Closed switch).
The --/-- indication is for OPEN (Open switch).
The message "Check H Connection" will be displayed.
NOTE: If both H and X connections are open, "Check H X connection" will
be displayed.
Low X Signal
Check Secondary (X) cables for inadvertent short.
Check to make sure the Secondary (X) cable is connected properly at the
instrument panel.
Secondary (X) winding may be shorted or the transformer circuit breaker
may be open or the ratio may be higher than the instrument can measure.
Low H Signal
Check Primary (H) cables for inadvertent short.
Check to make sure the Primary (H) cable is connected properly at the
instrument panel.
Primary (H) winding may be shorted.
Memory is Full! Data NOT stored
The instrument memory is full and there is no more location left for
additional storage.
Memory Error! Service Required
Measurement Records cannot be stored or recalled because the memory
cannot be accessed. Factory service is needed. However, the TR8703
can be used to make measurements in a normal manner.