4.3. Tips for Making Precise Ratio Measurements
The TR8703 is designed for step-down transformers. It sources low
voltage on the primary. It starts with a fraction of the final source voltage
and checks the secondary voltage.
If it exceeds the primary by a pre-determined value, the safety feature
stops the measurement. The recommended procedure is to reverse the
leads in these circumstances so that the primary of the transformer is
connected to the H cables and the secondary of the transformer is
connected to the X cables.
CAUTION: It is important to check that the H cables are connected
to the primary side and the X cables are connected to the
secondary side of the transformer before the test begins.
 Always verify the integrity of the cable connections and reposition the
clips as necessary for robust and low-resistance connections. Inspect
the transformer terminals for dielectric coatings, fungus, dirt or
corrosion
 Running a continuity test before the ratio test will provide a useful way
to check windings and connections
 When testing polyphase transformers, keep in mind that in some
cases, the measured ratios must be multiplied or divided by √3. Refer
to § 6 for polyphase connection diagrams and associated ratio
equations