JUMO flowTRANS MAG H20 Manual Breve página 57

Ocultar thumbs Ver también para flowTRANS MAG H20:
Idiomas disponibles

Idiomas disponibles

Modbus PDU
Data type
address
dec
hex
2430
97E
float
2431
97F
float
2433
981
selection
2334
982
float
2336
984
float
a
r/w: Read and write access
7.4
Actions
Modbus PDU
Data type
address
dec
hex
3000
BB8
action
3100
C1C
action
3150
C4E
action
3627
E2B
action
a
r/w: Read and write access
Number of
Ac-
a
Modbus
cess
registers
1
r/w
2
r/w
2
r/w
1
r/w
1
r/w
Number of
Ac-
a
Modbus
cess
registers
2
r/w
2
r/w
2
r/w
2
r/w
7 Modbus address tables
Data
LVS 4: Switching function
LVS 4: Hysteresis
LVS 4: Error behavior
LVS 4: Switch-on delay
LVS 4: Switch-off delay
Data
Save configuration
Reset totalizer
Start / stop batch function
Teach function
Encoding
0: Deactivated
1: Hysteresis mode
2: Window mode
3: Two-point mode
-20 °C to +90 °C
0: Inactive
1: Active
2: Frozen
0 s to 100 s
0 s to 100 s
Encoding
Save (0xc7e7bc2e)
Discard (0xf0864181)
Default setting (0x34bfe138)
Reset (0x650d33c0)
Start / stop (0x1c9e3727)
Teach SP1 (0x57fbe8)
Teach SP2 (0x35800a1)
25