Modbus PDU
Data type
address
dec
hex
1004
3EC
string
1014
3F6
string
1100
44C
selector
1106
452
selector
1112
458
selection
1113
459
integer
a
r/w: Read and write access
Analog input
Modbus PDU
Data type
address
dec
hex
1200
4B0
float
1211
4BB
float
1213
4BD
float
1217
4C1
boolean
1225
4C9
float
1227
4CB
float
1229
4CD
float
a
r/w: Read and write access
Modbus TCP
The following settings of the units concern the Modbus interface. For the display on the device, the units
can be set separately  "Display ", Page 20.
Modbus PDU
Data type
address
dec
hex
1600
640
integer
1602
642
selection
Number of
Ac-
a
Modbus
cess
registers
10
r/w
18
r/w
6
r/w
6
r/w
1
r/w
2
r/w
Number of
Ac-
a
Modbus
cess
registers
2
r/w
2
r/w
2
r/w
1
r/w
2
r/w
2
r/w
2
r/w
Number of
Ac-
a
Modbus
cess
registers
2
r/w
1
r/w
7 Modbus address tables
Data
Device name
DNS name
Process value 1
Process value 2
Display orientation
Display brightness
Data
Flow: Low flow suppression 0 % to 10 %
Flow: Filter time constant
Flow: Simulation value
Flow: Inversion
Temperature: Offset
Temperature: Filter time
constant
Temperature: Simulation
value
Data
Port gateway
Temperature unit
Encoding
Name to access the device in
the Ethernet network – instead
of the IP address
 "Analog selector ", Page 28
 "Analog selector ", Page 28
0: 0°
1: 90°
2: 180°
3: 270°
0 to 10
Encoding
(Input value as a percentage of
the maximum flow measuring
range)
0 s to 25 s
-0.00275 m³/s to +0.00275 m³/
s
-10 °C to +10 °C
0 s to 25 s
-22 °C to +99 °C
Encoding
1 to 1024
0: °C
1: °F
21