6. Electrical work
Thickness of Wire for Main Power Supply and On/Off Capacities
Power supply
Model
~ /N 220-230-240 V 50 Hz
~ /N 220 V 60 Hz
Outdoor unit
3N~ 380-400-415 V 50 Hz
3N~ 380 V 60 Hz
Indoor unit /
~/N 220-230-240 V 50 Hz
Branch box
~/N 220 V 60 Hz
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
Total operating current of the indoor unit
F0 = 16 A or less *2
F0 = 25 A or less *2
F0 = 32 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + ··· + {V1 × (Quantity of Type 15)/C}
Connect to Branch box (PAC-MK·BC)
Indoor unit
Type 1
PEAD-RP·JAQ(L).UK, PEAD-M·JA(L)
Type 2
SEZ-KD·VA, SEZ-M·DA, PCA-RP·KAQ, PCA-M·KA, PLA-RP·EA(.UK)
Type 3
SLZ-KF·VA, SLZ-M·FA
Type 4
MLZ-KA·VA, MLZ-KP·VF
Type 5
MSZ-LN·VG, MSZ-AP·VF, MSZ-AP·VG, MFZ-KJ·VE
Type 6
MSZ-FH·VE, MSZ-GF·VE, MSZ-SF·VE, MSZ-EF·VE, MSZ-SF·VA
Type 7
Branch box (PAC-MK·BC(B))
Connect to Connection kit (PAC-LV11M)
Indoor unit
Type 8
MSZ-LN·VG, MSZ-AP·VF, MSZ-AP·VG
Type 9
MSZ-SF·VA, MSZ-SF·VE, MSZ-EF·VE, MSZ-FH·VE
Type 10
Connection kit (PAC-LV11M)
Indoor unit
Type 11
PEFY-P·VMA(L)-E, PEFY-P·VMA3-E
PMFY-P·VBM-E, PLFY-P·VBM-E, PLFY-P·VEM-E, PLFY-EP·VEM-E, PLFY-P·VFM-E,
Type 12
PEFY-P·VMS1(L)-E, PCFY-P·VKM-E, PKFY-P·VHM-E, PKFY-P·VKM-E, PFFY-P·VKM-E,
PFFY-P·VLRMM-E
Type 13
PLFY-P·VCM-E
Type 14
PKFY-P·VBM-E
PLFY-P·VLMD-E, PEFY-P·VMH-E, PEFY-P·VMR-E-L/R, PEFY-P·VMH-E-F,
Type 15
PFFY-P·VLEM-E, PFFY-P·VLRM-E, GUF
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
20
Minimum Wire Thickness (mm²)
When power is supplied
separately
When power is supplied from
the outdoor unit
When power is supplied
separately
When power is supplied from
the outdoor unit
Refer to the following indoor unit or branch box wiring and breaker capacity calculation.
Minimum wire thickness (mm²)
Main Cable
Branch
Ground
1.5
1.5
1.5
2.5
2.5
2.5
4.0
4.0
4.0
4-·RD(H)4
✽
Breaker for
Wiring *1
Main Cable
Ground
6.0
6.0
6.0
6.0
2.5
2.5
4.0
4.0
Ground-fault interrupter *1
Capacity
20 A current sensitivity *3
30 A current sensitivity *3
40 A current sensitivity *3
V1
V2
26.9
19.8
17.1
2.4
9.9
7.4
6.8
5.1
3.0
V1
V2
7.4
6.8
2.4
3.5
V1
V2
38.0
1.6
19.8
2.4
9.9
3.5
0
0
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
16 A
16 A 30 mA 0.1 sec. or less
25 A
25 A 30 mA 0.1 sec. or less
Local switch (A)
Breaker for wiring
(NFB)
Fuse
16
16
20
25
25
30
32
32
40