E
MERGENCY RELEASE
Carry out only after power supply to the motor has been
interrupted!
In the event of a power supply failure, release the gearmotor, so that you
can move the boom by hand.
To do so, use the RIB key supplied and turn it in the clockwise sense,
until the stop is reached (Pic. 6).
By doing so, the barrier boom works independent from the gearmotor
and it can be moved by hand.
When power is supplied again, turn the key counterclockwise strongly
until you block it.
M
AINTENANCE
To be undertaken only by specialized staff after disconnecting
power supply.
After every 100.000 cycles check:
- boom balance (see the paragraph "ADJUSTING THE BALANCING
SPRINGS");
- the tightness of the release knob (see the paragraph "EMERGENCY
RELEASE");
- the tightness of the boom holding attachment and the implantation of
the boom (see the paragraph "ASSEMBLING THE BOOM");
- the wear on the mechanical stops and the limiti switch setting (see the
paragraph "LIMIT SWITCH SETTING").
- Grease the bearings of the boom carrier shaft and the threaded spring
guide bar.
The described maintenance is vital for the corrected operation of
the product in the time.
ELECTRIC CONNECTIONS
A
VAILABLE FUNCTIONS OF THE BUILT-IN EUROBAR
(VRS.05 or sup.) ELECTRONIC CONTROL BOARD
Automatic control
Step by step control
Operation in PARK modality
Exclusion of the total automatic close function
Microprocessor autotest on the security entries
Activation of the pre-flashing time
Activation of the gate open indicator led
Led or display to segnalise the board state
Slow speed in approach
Elettromagnet operation for barriers
Exclusion of photocells during opening
Control for 1 relay card to turn on the box lamp (OPTIONAL)
S2 - MICROSWITCHES FOR CONTROL UNIT SETTINGS
Dip1
For future use
Dip2
Flasher
ON
fixed output
OFF
flasher output
Dip3
Photocell
ON
stops movement during opening and closing
OFF
stops movement during closing only
Dip4
Operation mode
ON
park mode
OFF
normal operation
Dip5
Standby time prior to automatic closing (max. 5 min.)
ON
enabled
OFF
disabled
Dip 6
ON
Heater card control (Heater for EUROBAR v.07) code
ACQ9097
OFF
Magnet control (code ACG8070 - ACG8073)
To manage the Heater and the Magnet read carefully the specific
manuals.
S3 - RESET
Each time the position of dipswitches is changed, loop S3 for at
least one second or the board will not accept the new settings (also
possible using a screwdriver).
LED
L1
(Yellow) indicates secondary power supply (12Vdc)
L2
(Red) indicates time settings
J1 TERMINAL BOARD
NL1
230V 50/60 Hz power supply
J2 CONNECTOR
Via an optional card (Relay card 1 code no. ACQ9075) this connector
powers a garage light with a time setting between 1 second and 3
electric board EUROBAR
G G
B B
6