Wöhner MOTUS 30Compact Manual De Instrucciones página 15

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 28
Variant
General ata
Power dissipation min. / max.
Max. switching frequency (pulse / pause times 50:50)
Deactivation time via control supply voltage
Deactivation time via activation voltage
Activation time via activation voltage
Rate
urge voltage between control input, control upply
an
witching voltage
Nominal mains voltage (≤ 500V AC)
Nominal mains voltage (≤ 300V AC), e. g. 230 / 400V AC,
277 / 480 V AC
Nominal mains voltage (≤ 300 – 500V AC)
Control input, control upply voltage an reply output,
reply output an
witching voltage
Nominal mains voltage (≤ 500V AC)
Nominal mains voltage (≤ 300V AC), e. g. 230 / 400V AC,
277 / 480V AC
Nominal mains voltage (≤ 300 – 500V AC)
Ambient temperature range operation
Ambient temperature range transport, storage
Surge voltage category
Pollution degree
Standards/specifi cations
Power station requirement
Service life
Degree of protection
Mounting position
Mounting (see 9. Derating curve)
Hou ing:
Material
Dimensions incl. DIN rail adapter
Dimensions incl. power busbar adapter 30Compact
Dimensions incl. power busbar adapter 60Classic
Connection ata (con uctor cro - ection)
Screw terminal blocks (solid / stranded)
M3 thread, recommended torque
A apter connection ata
Connection Ø DIN rail adapter (solid / stranded)
Copper Ø Compact / Classic power busbar
Max. power busbar current
Weight
DIN rail adapter
6Power busbar adapter 30Compact
Power busbar adapter 60Classic
Certifi cation
EC type examination certifi cate to ATEX
Safety level
Contact · Wöhner GmbH & Co. KG · Elektrotechnische Systeme · Mönchrödener Straße 10 · D-96472 Rödental
Postal address PO Box 11 60 · D-96466 Rödental · Germany
Telephone +49 (0) 9563/751-0 · Fax +49 (0) 9563/751-131 · [email protected] · www.woehner.com
28
Max. 0.6A
Max. 2.4A
Max. 9A
0.88W / 2.8W
0.88W / 5.5W
0.88W / 12W
2Hz
type 25ms
max. 500ms
type 30ms
max. 80ms
type 40ms
max. 50ms
6kV
Safe isolation (EN 50178)
Safe isolation (IEC 60947-1)
Basic isolation (IEC 60947-1)
Safe isolation (IEC 60947-1)
Safe isolation (EN 50178)
Safe isolation (IEC 60947-1)
Basic isolation (IEC 60947-1)
– 25°C – + 70°C
– 40°C – + 80°C
III
2
IEC 60947-4-2 / IEC 61508-1 / ISO 13849-1/EN 954-1
DWR 1300 / ZXX01/DD/7080.8d
3 × 10
7
cycles
IP20
Vertical (horizontal DIN rail / busbar)
Can be mounted in rows with zero spacing or with ≥ 20mm spacing
PA 6.6
(22,5 / 175 / 138)mm (W/H/D)
(22,5 / 160 / 156)mm (W/H/D)
(22,5 / 200 / 156)mm (W/H/D)
See connection notes (page 22)
0.14 – 2.5mm²
AWG 26–14
0.5 – 0.6Nm
4.4 – 5.3 lb-in
0.2 – 6mm² / 0.2 – 4mm² (AWG 24–10)
5 (or 10) × 12mm / 5 (or 10) × 30mm
2500A
Approx. 368g
Approx. 374g
Approx. 377g
EX II (2) G [Exe] [Exd] [Expx]
EX II (2) D [Ext] [Exp]
PTB 13 ATEX 3001
See section 8.1 and 8.2
MOTUS®
Démarreur – Inverseur hybride.
Révision 5, version 03.2016
Françai .
29
Tabla de contenido
loading

Este manual también es adecuado para:

Motus 60classic

Tabla de contenido