Application Example - Wöhner MOTUS 30Compact Manual De Instrucciones

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 28
Manual (remote acknowle gement point)
Connect a button (N / O contact) between the MAN
and RES terminals.
An acknowledgement is triggered as soon as a positive
edge is detected at the MAN input - button pressed
briefl y. If a negative edge is not identifi ed after approx.
2s, the hybrid motor starter adopts the error status
again.
Automatic
Establish an electrical connection between the RES and
AUT terminals.
After the bimetal monitoring has been triggered and
the subsequent cooling, the device performs an auto-
matic acknowledgement.
The RES terminal provides the voltage for the reset.
In variants with a rated control supply voltage of 24V
DC, this is 24V DC.
Fee back
As soon as the hybrid motor starter detects an error, the
reply relay is switched, i.e. the N / O contact is closed or
the N / C contact is opened. This behavior corresponds
to that of a motor overload protection relay.
The feedback is for signaling purposes only and is not
part of the safety chain. It is thus not included in the
safety monitoring.
Parameterization –
Nominal current etting
Note: Thi function i only po ible if the evice i not
activate an there i no efect at the evice.
1. Make sure that the 24V DC control voltage is applied,
no R or L activation is taking place and that no error
message is displayed.
2. Open the cover.
3. Pre
the et / re et button for more than 6 to
change to the „Parameterization" mode – the green
PWR LED fl ashes once.
Note: In Parameterization mo e, the LED are
witche off every 2 for 0.3 to i tingui h thi mo e
from other operating mo e .
4. Set the nominal current of the drive using the 240°
potentiometer. The nominal current is specifi ed in
16 stages. The four LEDs show the set current.
5. Store this value by pressing the set / reset button
again (non-volatile area of the data memory).
24
6. Press the set / reset button for more than 2s (and
less than 6s) to display the set current for 3s.
4
3
5
6
1
2
Co e
Nominal current (mA)
PWR
ERR
L
R
0.6A
2A
9A
0
0
0
0
75
180
1500
0
0
0
1
110
250
2000
0
0
1
0
145
410
2500
0
0
1
1
180
560
3000
0
1
0
0
215
710
3500
0
1
0
1
250
870
4000
0
1
1
0
285
1020
4500
0
1
1
1
320
1170
5000
1
0
0
0
355
1330
5500
1
0
0
1
390
1480
6000
1
0
1
0
425
1630
6500
1
0
1
1
460
1790
7000
1
1
0
0
495
1940
7500
1
1
0
1
530
2090
8000
1
1
1
0
565
2250
8500
1
1
1
1
600
2400
9000
Note: If the motor current i above 45A, the block
monitoring i activate ( ee 9. Trigger characteri tic
curve an
erating curve).

6. Application example

Safety oor (EMERGENCY STOP)
In applications where the safety switch-off is a normal
operating mode, such as in the case of safety door or
two-hand applications, a circuit as per Fig. 4 should
be used. Here, the control circuit is switched off via a
safety relay as soon as the EMERGENCY STOP button is
actuated. If the switch-off is performed, for instance,
from a „safe controller" with semiconductor outputs,
the residual voltage must be < 5V DC. Interruptions
≤ 3 ms are fi ltered.
EMERGENCY STOP
Integrating a hybrid motor starter into an EMERGENCY
STOP chain is pictured in Fig. 5.
In this application, the control circuit is switched and
not the control supply voltage.
If the switch-off is performed, for instance, from a
„safe controller" with semiconductor outputs, the re-
2.1
/
24 V DC
2.1
/
GND
2.0 /
L1
/
2.0 /
L2
/
2.0 /
L3
/
S2
A1
S11 S12 S21 S22
L1 L2 L3
U
E
R L
PSR-SCP-24UC/ESA4/3X1/1X2/B
A2
97
96/98
MOTUS®ContactronControl
Re et
S3
MAN RES AUT
T1:2 T2:4 T3:6
U1
V1
W1
M
3~
PE
Fig. 4
Motor overloa protection
All safety-relevant functions are implemented by the hy-
brid motor starter, without external infl uences. Special
circuit technology is not necessary.
Wiring of the load current circuit should be realized as
described in the examples provided. The module cur-
rent supply can however be directly connected to the
voltage source, without the PSR safety relay. The same
is applicable for the control.
Motor with brake
If a motor with brake is connected (in the motor ter-
minal board), the 400V AC brake has to be connected
to the 2 / T1 and 6 / T3 connections. A 230V AC brake
must be connected with 4 / T2 and the neutral point
of the motor.
Note: The motor current monitoring mu t be increa e
by the value of the brake (nominal brake current).
Revision 5, status 03.2016
sidual voltage must be < 5V DC. Interruptions ≤ 3 ms
are fi ltered.
Note: Switching off the control voltage upply with
a controlle motor alway re ult in wear in the
hybri motor tarter! Thi
witch houl only be
u e if no more than 10,000 hut own can be
expecte over the entire life pan of the y tem. If
the witch-off i performe , for in tance, from a
„ afe controller" with emicon uctor output , the
re i ual voltage mu t be < 5V DC. Interruption
≤ 1m are filtere .
/
/
Permanent 1 supply
24 V DC
GND
Switched 2 supply
24 V DC
L1
/
GND
L2
/
L3
/
13 23 33 41
L1 L2 L3
U
E
R L
14 24 34 42
MOTUS®ContactronControl
MAN RES AUT
T1:2 T2:4 T3:6
U1
V1
W1
M
3~
PE
Fig. 5
Replacing fu e
The fuses are rated so that they only need to be re-
placed after damage. Mains outages or disconnection
of fuses will be signaled as a phase failure upon activa-
tion (PWR + Err fl ash and L or R light up).
1.
2
1
Engli h.
/
/
/
/
25
Tabla de contenido
loading

Este manual también es adecuado para:

Motus 60classic

Tabla de contenido