2.
1
2
3.
Spare fu e
0.6A an 2.4A variant
16A 31 567
Wöhner
16A 2903126
Phoenix Contact
16A FR10GR69V 16
Mersen
Note: The li te fu e provi e optimum hort circuit
protection an reliable control of the motor tarting
current . We recommen that you only u e the e fu e
type .
7. Technical ata
Variant
Input ata
Rated control supply voltage U
as per IEC 60947-1 / UL 508
s
Control supply voltage range
Control supply voltage, Switching level „Safe off "
Rated control supply current as per IEC 60947-1
Control input L, R:
Switching level „Low"
Switching level „Safe off "
Switching level „High"
Input current
26
4.
5.
Click
Spare fu e
9A variant
20A 31 568
Wöhner
20A 2903384
Phoenix Contact
20A FR10GR69V 20
Mersen
30A 31 569 *
Wöhner
30A 2903119 *
Phoenix Contact
30A CCMR30 *
Littelfuse
* I nee e for motor with heavy tarting.
Max. 0.6A
Max. 2.4A
Max. 9A
24V DC
19.2 – 30V DC (32V DC, max. 1 min.)
< 5V DC
≤ 40mA
-3 to 9.6V DC
< 5V DC
19.2 – 30V DC
≤ 3mA
Variant
Output ata
Switching principle
Rated operating voltage U
as per IEC 60947-1
e
Operating voltage range as per IEC 60947-1
Operating voltage range as per UL 508
Load current at 20°C (see chapter 9)
Rated operating current I
as per IEC 60947-1
e
AC-51 as per IEC 60947-4-3
AC-53a as per IEC 60947-4-2
as per UL 508 (see chapter 9)
Normal switching power as per UL 508
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
Leakage current (input, output)
Residual voltage at I
e
Surge current
Input protective circuit
Short circuit current rating SCCR as per
UL 508a (under preparation)
Reply output
Contact type
Contact material, in new condition
When u e a
Max. switching voltage
Min. switching voltage
Max. continuous load current Io
Min. switching current
Max. interrupting rating *, ohmic load 24V DC / 250V AC
Mea urement technology
in ref. to 9. Trigger characteristic curve
Two-phase current measurement, Range
Symmetry monitoring
Amount I
> I
=> (I
- I
/ I
)
max
nenn
max
min
max
Amount I
< I
=> (I
- I
/ I
)
max
nenn
max
min
nenn
Response time
Phase failure monitoring, I (L1), I(L3) typ.
Amount (angle (L1, L3))
Response time
Blocking protection, I (L1) oder I(L3)
Response time
Trigger characteristic (see chapter 9) as per IEC 60947
Cooling-down time
Operating element
Operating voltage indicator
Device and process error display
Activation display
Button
Potentiometer for nominal motor current setting
* Other available on reque t.
Revision 5, status 03.2016
Engli h.
Max. 0.6A
Max. 2.4A
Max. 9A
Safety output module with bypass,
three-phase electrically isolated shutdown
500V AC (50 / 60Hz)
42 – 500V AC symmetrical
0.075 – 0.6A
0.18 – 2.4A
1.2 – 9A
0.6A
2.4A
9A
0.6A
2.4A
6.5A
0.6A
2.4A
6.5A
0.3kW (0.4HP)
0.9kW (1.2HP)
2.3kW (3.0HP)
0.5kW (0.6HP)
1.7kW (2.2HP)
4.6kW (6.1HP)
0mA
< 300mV
< 400mV
< 500mV
100A (t = 10ms)
Varistors, fuses
With fuse class J (30A), suitable for use in circuits, that do not
supply more than 100kA
symmetrical current, max. 500V
eff
Single contact, 1PDT contact
Ag alloy, hard gold-plated
Signal contact
Power contact
30V AC / 36V DC
250V AC / DC
100mV
12V AC / DC
50mA
6A
1mA
10mA
1.2W / –
140W / 1500VA
0.07 – 0.6A
0.18 – 2.4A
1.5 – 9A
≥ 33% / ≥ 67%
≥ 33% / ≥ 67%
≥ 33% / ≥ 67%
≥ 33% / ≥ 67%
≥ 33% / ≥ 67%
≥ 33% / ≥ 67%
2min. / 1.8s
> 75mA
> 150mA
> 1200mA
170 – 190
< 1.8s
–
–
> 45A
–
–
2s
Class 10A
20min.
LED PWR (green)
LED Err (red)
LED L (yellow) / LED R (yellow)
Error acknowledgement
240°
27