REMS Multi-Push S Instrucciones De Servicio página 25

Ocultar thumbs Ver también para Multi-Push S:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 63
eng
REMS NoCor is suffi cient for a volume of approx. 100 l. REMS CleanH is dyed
green in order to be able to check fi lling and washout, REMS NoCor is dyed
blue to check fi lling. The safety data sheets for REMS CleanH and REMS
NoCor under www.rems.de → Downloads → Safety Data Sheets as well as
other local and national regulations must be observed.
NOTICE
NOTICE
Never allow cleaner or corrosion protection agent to fl ow though the pipes of
REMS Multi-Push.
Do not use suction/pressure hoses for drinking water lines any more after they
have been used for heating systems.
The built-in nozzles for automatic dosing by REMS V-Jet TW and REMS V-Jet
H are different and are adapted to the properties of the REMS ingredients to
be injected. Therefore please always observe the intended use.
2.8 Compressed air pump program (REMS Multi-Push SL/SLW)
Vessels of all types can be pumped up with this program. Connect the compressed
air hose (23) to the output Pressure test with compressed air, Compressed air
pump (Fig. 4 (22)) and connect it to the vessel to be pumped up, e.g. expansion
vessel, tyre. The value 0.02 MPa / 0.2 bar / 3 psi is preset.
2.9 Memory Manager program (data transfer)
The results of the fl ushing and test programs are saved with date, time and log
number in the selected language and can be transferred to a USB stick or
printer (accessory part no. 115604) (neither of which is included in the scope
of supply) for documentation (see 3.8).
2.10 Compressed air tools connection
Unlike the described "Compressed Air Pump" program in which the values are
controlled by the electronic control, compressed air tools up to a max. air
requirement of 230 Nl/min can be operated directly from the compressed air
vessel at the compressed air tools connection (Fig. 4 (28)). A compressed air
hose with quick couplings NW 7.2 must be used (accessory part no. 115621).
3 Operation
NOTICE
NOTICE
REMS Multi-Push is not intended/suitable for permanent connection to the
installation. Disconnect all hoses from the installation after completing the work.
REMS Multi-Push may not be operated unattended.
Before using the REMS Multi-Push, check whether the respective latest version
software is installed on the input and control unit. For REMS Multi-Push S the
use of software version as of "03.40, Date 2020-04-08" is permitted. Select the
Settings menu and then Device data to display the version software. The latest
version software (Ver. Software) for the input and control unit is available by
USB stick as a download: www.rems.de → Downloads → Software → REMS
Multi-Push → Download. Compare the number of the version software of the
unit with the latest version software number and install the latest version soft-
ware if necessary.
Download procedure:
1. Download fi le
2. Unpack the ZIP fi le
3. Save "update.bin" on USB stick
4. Plug the USB stick into the USB port of the REMS Multi-Push
See 2.3 for the further procedure.
NOTICE
NOTICE
The defaults for the different test criteria (test sequences, pressures and times)
in the settings menu of the REMS Multi-Push SL/SLW are taken from EN
806-4:2010 or the information leafl et "Leak tests of drinking water installations
with compressed air, inert gas or water" (January 2011) of the German Central
Association for Sanitary, Heating and Air Conditioning (ZVSHK). All defaults
for the test programs can be edited by the user in the Settings menu and in the
Flushing, Test with compressed air, Test with water and Compressed Air Pump
programs. Changes in the Settings menu are saved, i.e. they reappear the next
time the REMS Multi-Push SL/SLW is switched on. If the defaults are only
changed in one of the programs, the original defaults appear again the next
time the REMS Multi-Push SL/SLW is switched on. Reset resets all defaults to
factory settings and the language to German (deu) and the date, time, units
formats to DD.MM.YYYY, 24 h, m/bar.
Attention: The user is solely responsible for transferred or newly entered
test criteria (test sequences, pressures and times) or defaults in the
individual programs and the conclusions from the tests. Especially, the
user must decide whether a prescribed stabilisation/wit time is ended
and must confi rm this by \Enter.
The respective national safety provisions, rules and regulations valid for
the application site must be considered and observed.
The electronic memory of REMS Multi-Push holds 40 fi les (logs). A soon as a
program has been selected from the Start menu and the selected data have
been confi rmed with Enter, a new fi le no. is created automatically even if the
program is then aborted e.g. with Esc. If the 40th memory location is occupied,
the message "Last fi le no. available". After completing this process, all fi les
should be copied to a USB stick via the USB port (Fig. 2 (33)). The oldest fi le
no. in the memory is then overwritten when further fi les are saved.
Screen display (must be released by Enter):
000425
Consecutive fi le no. 000425
19.08.2013 10:13
Date 19.08.2013 Time 10:13 (creation of a new fi le no.)
Files 40/40
Files 40/40 (a max. of 40 fi les are saved)
Last fi le no.
Last fi le no.
available
available
3.1 Programs fl ush EN 806-4 drinking water installations, program fl ush/desilt
radiators and area heating systems
In EN 806-4:2010 and for Germany additionally in Technical Rules – Worksheet
DVGW W 557 (A) October 2012 of the DVGW German Association of the Gas
and Water Industry e.V. and in the information leafl et "Flushing, disinfection
and commissioning of drinking water installations" (August 2014) of the German
Central Association for Sanitary, Heating and Air Conditioning (ZVSHK) the
fl ushing methods "fl ushing with water" and "Flushing with water/air mixture with
pressure surges" are described. REMS Multi-Push additionally offers the fl ushing
program "fl ushing with water/air mixture with constant compressed air".
Excerpt from EN 806-4:2010, 6.2.1 "The drinking water installation must be
fl ushed with drinking water after installation and pressure testing as well as
immediately before commissioning." "If a system is not put into operation imme-
diately after commissioning, it must be fl ushed at regular intervals (up to 7 days)."
3.1.1 Program fl ush EN 806-4 with water (without air supply)
Program fl ush EN 806-4 with water (without air supply)
In accordance with EN 806-4:2010 and for Germany
with the Technical Rule – Worksheet DVGW W 557 (A) October 2012 of the
DVGW German Gas and Water Association and the information leafl et "Flushing,
disinfection and commissioning of drinking water installations" (August 2014)
of the Central Association for Sanitary, Heating, Air Conditioning (ZVSHK),
Germany, the drinking water used for fl ushing must be fi ltered and must be of
perfect drinking water quality. Filters must hold back particles ≥ 150 µm (Use
REMS fi ne fi lter with fi lter cartridge 90 µm, Art. No. 115609). The system must
be fl ushed section for section depending on the size of the installation and the
arrangement and lay of the pipes. Flushing must be start on the bottom fl oor
of the building and continue upwards in lines, within a line fl oor by fl oor, i.e.
from the nearest to the furthest line and fl oor. The minimum fl ow velocity when
fl ushing the installation must be 2 m/s and the water in the system must be
replaced at least 20 times during fl ushing.
Within the fl oor and single lines, at least as many tapping points as listed in the
following table as a recommended value for a fl ushing section will be fully
opened for at least 5 minutes fl oor by fl oor.
Greatest rated width of the pipe in the
fl ushed section, DN
Greatest rated width of the pipe in the fl ushed
section, in inches
Minimum number of tapping points to be
opened DN 15 (½")
Table 1: Recommended value for the minimum number of tapping points to be
opened related to the greatest rated width of the distribution line" (single tapping
rate at least 10 l/20 s) (Information leafl et "Flushing, disinfection and commis-
sioning of drinking water installations" (August 2014) of the German Central
Association for Sanitary, Heating and Air Conditioning, lines in italics added,
limiting to DN 50). Two or more REMS Multi-Push can be connected in parallel
to fl ush greater rated widths.
REMS Multi-Push displays the achieved fl ow velocity and the achieved water
change on the screen among other things.
Program sequence ↑ ↓ (8):
1. Flush \ Enter
2. Flush EN 806-4 \ Enter
3. without compressed air \ Enter
4. Check default max. DN according to table 1 and change if necessary (11) \ ↓
5. Enter water volume of the fl ushing section VA H
Fig. 6)
6. Open the water supply. The values fl ash as long as the minimum fl ow
velocity v H
O = 2 m/s and the water change n H
2
reached. On reaching the values \ Enter
(If the defaults v H
O and n H
2
cause, repeat the process)
7. Display screen: Water pressure (p H
fl ushing time (t H
O), water change (n H
2
\ Enter
8. Esc >> Start menu \ Memory Manager, data transfer >> 3.8
3.1.2 Program fl ush EN 806-4 with water-air mixture with intermittent compressed
Program fl ush EN 806-4 with water-air mixture with intermittent compressed
air
The cleaning effect by fl ushing can be reinforced by adding compressed air. In
accordance with EN 806-4:2010 and information leafl et "Flushing, disinfection
and commissioning of drinking water installations" (August 2014) of the German
Central Association for Sanitary, Heating and Air Conditioning (ZVSHK), the
drinking water used for fl ushing must be fi ltrated whereby particles ≥ 150 µm
must be held back and the water must be perfectly fi t for drinking (REMS fi ne
fi lter with fi lter cartridge 90 µm, Art. No. 115609). "The pipe system can be fl ushed
under pressure with a drinking water/air mixture intermittently with a minimum
Germany additionally in accordance
25
32
40
1"
1¼"
1½"
2
4
6
O (0-999 l) \ Enter (see
2
O = 20 have not been
2
O are not reached: \ Esc = cancel, clarify the
2
O), minimum fl ow velocity (v H
2
O), volume of used water (V H
2
eng
50
2"
8
O),
2
O)
2
25
Tabla de contenido
loading

Este manual también es adecuado para:

Multi-push slMulti-push slw

Tabla de contenido