Presentation

5. Electrical connection

Refer to the electrical connection diagram located on the penultimate page.
The water heater must only be electrically connected once it is filled with water.
The water heater requires an uninterrupted power source.
The water heater can only be connected to and operated via a single-phase 230 V AC. Connect the water
heater using a rigid conductor cable with a 1.5 mm² cross-section. The installation must include:
• An all-pole 16 A circuit breaker with a minimum opening gap of 3 mm,
• Protection by a 30 mA earth-leakage circuit breaker.
If the power cable is damaged, it must be replaced by the manufacturer, its customer service or a professional
with similar qualification to prevent any hazards.
Never provide direct power supply to the heating element.
In no case should the safety thermostat on the electric heating element be repaired outside our factories.
Failure to comply with this clause will void the warranty.
The appliance must be installed in accordance with the national rules regarding electrical installations.
Electrical connection diagram
Earthing is mandatory.