4. USER INTERFACE (continued)
4.2 Water flow setting
With the water entry and exit valves being open, adjust the by-pass valve
in order to obtain a difference of 2°C between the water inlet and outlet
temperatures (see principle diagram § 3.1).
You can verify the switch by seeing the entry/exit temperatures directly on the
control panel.
Water outlet temperature
Water inlet temperature
Then, adjust your by-pass in order to obtain a difference of 2°C between the
input and the output.
Press
to exit the menu.
•
Opening the "bypass" valve generates a lower flow rate in the heat
pump exchanger, resulting in an increase in the inlet / outlet temperature
difference.
•
Closing the "bypass" valve generates a greater flow rate in the heat
pump exchanger, resulting in a reduction in the inlet / outlet temperature
difference.
The setting can be checked by viewing the inlet / outlet
temperatures (1 - 2) directly on the "EyesPool Inverter Connect"
application (see § 4.6).
14
OFF
ON
C
OUT
IN
1
2