Water Flow Setting - Hayward ENERGYLINE PRO INVERTER Serie Manual De Instrucciones

Unidad de bomba de calor para piscinas
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 72
3. INSTALLATION AND CONNECTION (continued)

3.6 Water flow setting

With the water entry and exit valves being open, adjust the by-pass valve in
order to obtain a difference of 2°C between the inflow and outflow temperature
(see principle diagram § 3.1). You can verify the switch by seeing the entry/
exit temperatures directly on the control panel.
Note: Opening the by-pass valve creates a weaker flow, which leads to an
increase in ∆T.
Closing the by-pass valve creates a stronger flow, which leads to a
decrease in ∆T.
12
Water inlet temperature
Water outlet temperature
Tabla de contenido
loading

Este manual también es adecuado para:

Enpi4mEnpi6m

Tabla de contenido