Ext. Input 2 Current
Offset (L1/L2/L3) [A]
External Meter
This setting specifies whether an external energy
Support
meter is connected for additional consumers
Main Distribution
Upper current limit for load management and for
Limit (L1/L2/L3) [A]
additional consumers
External Load
Safety margin for volatile consumers (in A).
Headroom (L1/L2/
Subtract this value from the value in the parame-
L3) [A]
ter "Main Distribution Limit (L1/L2/L3) [A]" to obtain
the maximum upper current limit of the charging
infrastructure
External Load
Upper current limit if no external energy meter is
Fallback (L1/L2/L3)
connected
[A]
External Meter
This setting specifies how the external energy
Location
meter is connected
External Load
Setting that specifies the duration (in seconds) to
Averaging Length
be used for determining the average of the exter-
[sec]
nal energy meter
Current Imbalance
This setting specifies whether current imbalances
Prevention
should be limited. The individual phase currents
are limited so that the value difference between
the individual phase currents does not exceed
the value for "Current Imbalance Limit"
Current Imbalance
Maximum value difference between individual
Limit
phase currents (in A)
Minimum Current
Lower current limit which is not exceeded when
Limit [A]
charging
Disconnected Limit
Current limit if no DLM network is connected
[A]
Clear persistent
Deletes the database of the known DLM-Satellite
DLM slave DB
Not relevant for the device
Charging
system
The external energy meter
has to be connected to the
router or switch via an ethern-
et cable.
Only if "External Meter
Support" = "On"
This value is higher than
the value for "EVSE Sub-
Distribution Limit"
Only if "External Meter
Support" = "On"
Only if "External Meter
Support" = "On"
Only if "External Meter
Support" = "On"
"Including EVSE Sub-
Distribution": Used to
detect charging points and
additional consumers
"Excluding EVSE Sub-
Distribution": Used to
detect charging points only
Only if "External Meter
Support" = "On"
Preset: "5"
Only if "Current Imbalance
Prevention" = "On"
The database must be deleted
when a DLM-Satellite is
decommissioned
EN
27