5.3 Preliminary tasks on the indoor
installation
T
DANGER
Fire hazard due to overload
There is a fire hazard caused by unsuitable circuit breaker
and supply line.
f Configure the circuit breaker and the supply line accor-
ding to the technical data and the configuration of the
device.
Î "4 Technical data"
5.3.1 Laying the supply line
f Configure the supply line according to the technical
data of the device.
Î "4 Technical data"
When dimensioning the supply line (cross sec-
tion and cable type), always ensure the following
local conditions:
Type of installation
Cable parameters per unit length
Line length
f Lay out the supply line to the desired location. The
device can be mounted on a wall or an stainless steel
or concrete column from MENNEKES.
Wall installation - surface installation
For a surface installation, the pre-punched aperture on the
upper enclosure part must be broken out.
Wall installation - concealed installation
For concealed installation the position of the supply line
must be arranged using the provided drilling template or
Fig. "Fig. 10: Drilling dimensions [mm]".
Mounting on a stainless steel or concrete column
If need be the device can be mounted on a stainless steel
or concrete column.
The stainless steel or concrete columns are available from
MENNEKES as accessories.
Installation manual for the stainless steel or concrete
column.
Mounting on a pole
If needed, the device can be mounted onto a pole. The
pole is available at MENNEKES as an accessory.
Installation manual from the pole
5.3.2 Providing fuse protection
Depending on the version, the device is equipped with
a type A residual current device, a circuit breaker and a
relay for connection of an external shunt release
according to the table below.
Circuit breaker
Type A residual current device
Relay for shunt release