Expansion Modules
If there is an error in the PT100 wiring or the input channel is open, the value read by
CLIC-02/4PT will be outside the expected range. Thus, CLIC-02 will neither update nor
store the channel value and the M error marker corresponding to the channel will be set.
11.4 COMMUNICATION EXPASION MODULES
11.4.1 Modbus Module
Summary
The module CLIC-02/MBUS allows a CLIC-02 to communicate with other devices via
Modbus protocol, in both the master and the slave modes. CLIC-02/MBUS works as a
Modbus slave node, responding to the requests of the network master, which makes its
scan circle become greater. Normally, the cycle time is lower than 20ms, but it increases
when the CLIC-02 processes a request from the master. For example, to write the setting
value of a function, the scan cycle can reach approximately 100ms.
Configuration of the Module CLIC-02/MBUS
176 | CLIC-02
Expansion Module 4PT Features
Temperature input range -100 °C~600 °C(-148°F~1112°F)
Digital output
Resolution
Variation
AT Channel
Marker
Number
M34
AT01
M35
AT02
M36
AT03
M37
AT04
- English -
-100 °C~600 °C(-148°F~1112°F)
2.5 mV
±0.5 %
Description
Channel 1 with error
Channel 2 with error
Channel 3 with error
Channel 4 with error
Supply terminals
Brackets for direct assembly
SW2 – Selection switch of the
terminating resistor
LED Run – Running Indication Module
LED COM – Port Activity Indication
LED ERR - Error Indication Module
SW1- 8-key set for adjustment
of the communication format
Port RS-485
Assembly lock