5 Installation

5.1.1
5.1.2
Required tools and
materials
26
| Conergy recommends the fuses listed below (observe local
regulations):
Level of performance
Conergy IPG 40K
Conergy IPG 60K
Conergy IPG 80K
Conergy IPG 100K
Conergy IPG 110K
Conergy IPG 280K
Conergy IPG 300K
| Make sure that the grid voltage stays within the specified limit
(see Chapter 3.5, page 18).

Connection cross-sections

The connection cross-section for all Conergy IPG series central
inverters depends on the desired voltage drop and on the cable
routing system.
The following table shows the minimum and maximum cross-
sections for the connecting cables:
Level of
Solar generator
performance
(DC, terminals 1–
3)
Conergy IPG
35–95 mm²
40K–60K
Conergy IPG
Unlimited maximum cross section, connection
80K–300K
via M12 cable lugs
Connecting the Conergy IPG 40K–60K
The installation procedure is identical for Conergy IPG 40K–60K
central inverters.
| Torque wrench for Allen bolts (Allen key), 6 mm, with handle
| Cable stripping knife, insulation removal tool
| Torque wrench for size 17 bolts
| Slotted screwdriver for auxiliary power supply
| M12 cable lug
cable lugs must be of the correct size for the cable sections
used.
| Tool for crimping the cable lugs
Operating manual
Fuse rating
Fuse type
63 A
GL NH00
100 A
GL NH00
125 A
NH1
160 A
NH1
160 A
NH1
400 A
NH3
630 A
NH3
Grid (AC)
35–95 mm² 1.5–2.5 mm²
Conergy IPG series central inverters
Auxiliary power
supply (230 V)
)
AC