Technical Description; Scope Of Supply; Functional Description - Conergy IPG Serie Instrucciones De Servicio

Ocultar thumbs Ver también para IPG Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

3

Technical description

3.1
Completeness
Transportation damage
3.2
Conergy IPG 40K–280K
Conergy IPG 300K
Conergy IPG series central inverters

Scope of supply

| Central inverter
| Operating manual
| Terminating resistor
| 2 bus plugs in the housing
| Test report
| Declaration of Conformity
Check the scope of supply for completeness. If the scope of
supply is incomplete, contact the manufacturer (contact details on
the back of the manual).
If you discover damage caused by transportation, contact the
manufacturer (contact details on the back of the manual).

Functional description

Conergy IPG 40K–280K central inverters have an integrated
transformer for transmitting the energy produced and are designed
to be connected to TN grids.
The Conergy IPG 300K central inverter is an inverter without an
integrated transformer which means there is no galvanic isolation
between the solar generator and the electricity grid. As a result, the
overall system efficiency of a PV system increases by up to 2%
The Conergy IPG 300K is designed for grid connection to a
medium voltage transformer and must only be operated in IT grids.
The connection is three-phase with 270 V from the medium voltage
transformer.
The interlinked output voltage is 270 V (156 V phase against N). A
transformer with galvanic isolation is therefore required to connect
the inverter to the electricity grid. A transformer must be provided
for each Conergy IPG 300K, or the transformer must have a
galvanically isolated winding for each device. Combining the
Conergy IPG 300K with the other Conergy IPG series devices is
only then possible if appropriate transformers are used. Except for
the transformer already mentioned, design and operation
correspond to the Conergy IPG 280K. When designing the fuses
1) Reference value, dependent on the PV system.
Operating manual
3 Technical description
1
.
11

Hide quick links: