4
Set the check operation (without initial refrigerant decision)
following setting mode 2 in the field setting and perform the
check operation.
The system operates for ±30 minutes and automatically stops
the check operation.
If no malfunction code is displayed on the remote controller
after the system has stopped, check if the operation is
completed. Normal operation will be possible after 5 minutes.
If a malfunction code is displayed on the remote controller,
correct the malfunction and perform the check operation
again as decribed in "Correcting after abnormal completion
of the test operation" on page 26
In case refrigerant was added without using the leak
detection function (pre-charging, charging in heating mode)
In the check operation, the following checks and judgement will
be performed:
Check of the stop valve opening
Check for wrong wiring
Check of refrigerant overcharge
Judgement of piping length
It takes ±40 minutes to complete the check operation.
Perform the test operation as decribed in the paragraph "Test
operation procedure" on page 26.
Test operation procedure
1
Close all front panels except the front panel of the electric box.
2
Turn ON the power to all outdoor units and the connected indoor
units.
Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.
3
Make the field setting as described in the paragraph "12.3. Field
setting" on page 23.
4
Press the
button once, and set to the SETTING
BS1 MODE
MODE (H1P led = OFF).
5
Press and hold the
BS4 TEST
more. The unit will start the test operation.
The test operation is automatically carried out in cooling
mode, the H2P led will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.
It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.
During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the led display may change, but these are not mal-
functions.
During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the
BS3 RETURN
±30 seconds.
6
Close the front panel in order to let it not be the cause of
misjudgement.
7
Check the test operation results by the led display on the
outdoor unit.
H1P H2P H3P H4P H5P H6P H7P
x x w x x x x
Normal completion
x w w x x x x
Abnormal completion
8
When the test operation is fully completed, normal operation will
be possible after 5 minutes.
Otherwise, refer to "Correcting after abnormal completion of the
test operation" on page 26 to take actions for correcting the
abnormality.
U-5~18MX4XPQ
Urban Multi air conditioner
4PW28163-1C
button down for 5 seconds or
button. The unit will stop after
Correcting after abnormal completion of the test operation
The test operation is only completed if there is no malfunction code
displayed on the remote controller. In case of a displayed malfunction
code, perform the following actions to correct the abnormality:
Confirm the malfunction code on the remote controller
Installation error
Error code
The stop valve of an
E3
outdoor unit is left
E4
closed.
F3
UF
The phases of the
U1
power to the outdoor
units are reversed.
No power is supplied
U1
to an outdoor or
U4
indoor unit (including
phase interruption).
Incorrect
UF
interconnections
between units
Refrigerant
E3
overcharge
F6
UF
For the U-5~18MX4,
U7
the wiring is
UF
connected to the
Q1/Q2 (Out Multi)
Insufficient refrigerant
E4
F3
After correcting the abnormality, press the
and reset the malfunction code.
Carry out the test operation again and confirm that the
abnormality is properly corrected.
Remedial action
Check referring to the table in
"Additional refrigerant charge" on
page 17
Exchange two of the three phases
(L1, L2, L3) to make a positive
phase connection.
Check if the power wiring for the
outdoor units are connected
correctly.
(If the power wire is not connected
to L2 phase, no malfunction display
will appear and the compressor will
not work.)
Check if the refrigerant line piping
and the unit wiring are consistent
with each other.
Recalculate the required amount of
refrigerant from the piping length
and correct the refrigerant charge
level by recovering any excessive
refrigerant with a refrigerant
recovery machine.
Remove the wiring from the Q1/Q2
(Out Multi).
Check if the additional refrigerant
charge has been finished correctly.
Recalculate the required amount of
refrigerant from the piping length
and add an adequate amount of
refrigerant.
button
BS3 RETURN
Installation manual
26