6. Search for faults

EN
Voltage absent. Start-up relay with open
contacts.
A
Thermal protection trips.
Loosened or incorrect electrical
connections.
Compressor does not start (releases humming sound) and the thermal protector trips
Incorrect electrical connections.
Low voltage on compressor.
Defective condenser start-up.
B
Relay does not close
Electrical motor with interrupted winding
or short-circuited.
Incorrect electrical connections.
Low voltage on compressor.
Relay locked in closed position.
C
Excessive discharge pressure
Electrical motor with interrupted winding
or short-circuited.
Low voltage to compressor (imbalanced
phases on three-phase motors).
Defective thermal protection.
Defective drive capacitor.
Excessive discharge pressure
D
Suction pressure too high.
Compressor overheated, hot return flow
gas.
Compressor motor winding short-
circuited
Thermal protector.
Thermal switch.
High pressure switch intervention, due to
E
insufficient cooling on condenser.
High pressure intervention due to
excessive load of refrigerant gas.
Low pressure switch intervention due to
poor refrigerant gas load.
66 / 168
POSSIBLE CAUSE
The compressor does not start and does not release a humming sound
The compressor starts but the relay does not open
Compressor starts and rotates with brief operating cycles
Co2Nnext
Check the line or replace the relay.
Check the electrical connections again.
Tighten the connections or reconnect,
as shown in the wiring diagram.
Reconnect.
Identify the cause and eliminate it.
Identify the cause and replace the
condenser.
Identify the cause and replace the relay
if necessary.
Replace the compressor.
Check the electrical circuit.
Identify the cause and eliminate it.
Identify the cause and eliminate it.
Identify the cause and replace the
relay if necessary.
Replace the compressor.
Thermal protector tripping
Identify the cause and eliminate it.
Check its specifications and replace it if
necessary.
Identify the cause and eliminate it.
Check ventilation and possible strictures
or obstructions in the system circuit.
Check system sizing. Replace the
condensing unit with a more powerful
one if necessary.
Check the refrigerant load, repair
possible leakage, and add gas if
necessary.
Replace the compressor.
See previous point (thermal protector
tripping).
Small differential; correct adjustment.
Check the correct operation of the fan
motor or clean the condenser.
Lower refrigerant gas.
Repair leakage and add refrigerant
gas.
REMEDY