5 Commissioning
Possible (permissible) assignment
combinations for slots X14, X16
SMser
No module
1 module
SM24V
SMpdp
SMdev
2 modules
SM24V
SM24V
SM24V
SM24V
SM24V
SM24V
SMpdp
SMpdp
SMpdp
SMdev
SMdev
SMdev
Table 5:
Electric Drives and Controls | Bosch Rexroth AG 15/48
SMser
SM24V
SM24V
X14
X16
SM24V
SMpdp
SMibs
SMibs
SMser
SMser
SMeth
SMeth
SMdev
SM24V
SMpdp
SMibs
SMdev
SMser
SMeth
SM24V
SMser
SMeth
SMibs
SM24V
SMibs
SMser
SMibs
SMeth
SM24V
SMser
SMeth
SMser
SM24V
SMser
SMpdp
SMser
SMibs
SMser
SMdev
SMeth
SM24V
SMeth
SMpdp
SMeth
SMibs
SMeth
SMdev
SMpdp, SMdev, SMibs, SMeth and SMser
can each be used only once.
Only hardware version 2.1 is permitted in the
KE312 with SMeth (Fig.5).
Figure 5:
For safety and EMC reasons, close off slots
that are not occupied by Rexroth interface
modules with BP302 dummy panels, order
no. 3 608 871 392.
3 Min
Insert the modules into the communication
unit from the front and secure them with bolts
against unintended loosening.
Before inserting the in-
terface modules, the
system box must be
switched to neutral
and a discharging time
of ≥ 3 minutes must be
taken into account.