Figure 3-3 Clearances around the Generator Set for
The clearances around the generator set for cooling, service and maintenance
are shown in Figure 3-3. The clearance above the set is at least 2 meters. A is the
generator set. B is non-combustible material with fire resistant rating of 1 hour or
greater. C is combustible material or structure with a fire resistance rating of less than
1hour. D is any structure or material.
Do not connect B and/or C to D or else, it may cause fire.
3.3.2 Air Requirements
When installing the generator sets, great care must be taken to ensure adequate
ventilation. Proper installations require enough ventilation to cool the generator set as
well as supply adequate air for combustion. The air intake and exhaust should be in
line to provide engine room ventilation air flow which will parallel the generator set air
flow over the engine, through the generator and the radiator. The inlet and outlet
openings must be large enough to provide the volume of air required by the generator
set.
3.4 Product Storage
Long time storage is harmful to both engine and generator. It can minimize the
harm by properly preparation and storage of the generator set.
Cooling, Service and Maintenance
WARNING
18