Make sure that the emergency stop button is not pressed.
1.10 Precautions after Starting
Check the abnormal noise or vibration on the generator set.
Check the leakage of the exhaust system.
Monitor the generator set operation by way of the control module.
Check the engine temperature and oil pressure. The oil pressure must reach the
normal value after the generator set running 10 seconds.
Monitor the generator set outlet voltage and frequency.
If not equipped with jacket water heater, operate the generator set at no-load for 8
minutes before applying the load (manual mode).
1.11 Generator Set Isolating for Maintenance
When you service or repair a generator set, attach a "DO NOT OPERATE" or
similar warning tag which is shown as figure 1-1 to the generator set starting switch
and disconnect the generator set from the distribution system.
1.12 Accidental Starting
The generator set could start at any time in the "AUTO" mode. Keep clear of all
moving parts and be sure to turn switch to the "OFF" position before servicing and
disconnect the negative battery cable after disconnecting the battery charger circuit.
2. PRODUCT INFORMATION
2.1 Nameplate
Be ready to provide the generator set model and serial numbers on the
nameplate when contacting us for parts, service and product information. Figure 2-1
illustrates the nameplate. It also shows active power, apparent power, nominal voltage,
nominal current, power factor, phase number, frequency, insulation class, protection
class, weight, production date, size (length × width × height) and standard number.
Figure 1-1 Warning Tag