Quick Start Programming: steps 1, 2 and 3
Notes:
•
P000 locks the unit. The unlocking value is 1954: all other values lock the unit.
•
Default settings in the tables below are shown with an asterisk.
•
Please refer to the full Instruction Manual to set up inputs, communications, and other
functionality.
1.
Configure all parameters to their factory settings via P999 Master Reset:
a.
Press
to activate PROGRAM mode.
b.
Press
twice to access parameter fields.
c.
Key in 999.
d.
Press
e.
Reset complete. (Note: Reset takes several seconds to complete.)
2.
Set the following parameters for a Quick Start:
3.
P001 Operation: Sets the type of
measurement required for the
application.
1
Material Level
2
Space
Values
3 * Distance (flange face to material)
P002: Material
1 * Liquids or slurries
Value (view only)
P003 Measurement Response: Determines
level change reaction.
1
Slow
2 *
3
Values
4
5
Fast
7ML19985QA85
to Clear All and initiate reset.
0.1 m/min
1 m/min
10 m/min
100 m/min
1000 m/min
SITRANS LR300 – QUICK START MANUAL
P004 Antenna: Identifies antenna
configuration.
240 * factory setting for all antenna types
Val-
241
rod + 50 mm PTFE extension
ues
242
rod + 100 mm PTFE extension
P005 Units: Specifies units used for
dimensional values.
1 * Meters
2
Centimeters
3
Millimeters
Values
4
Feet
5
Inches
P006 Empty: Distance in Units (P005) from
flange face to process empty point.
Range: 0.000 to 9999
Preset:10 m (or equivalent
Values
depending on units)
(Empty level can be set at any distance
desired, not just actual empty.
P007 Span: Sets the range levels to be
measured.
Range: 0.000 to 9999
Preset: 10 m (or equivalent
Values
depending on units)
(Full level can be set at any measurement
above the empty level.)
)
Page EN-7