Clause / Requirement
13 Emergency microphone - Optional function
13. 1 General
c
The emergency microphone control shall mute alert and
evacuate signals within the selected emergency loud-
speaker zone.
d
Use of the emergency microphone shall not reset an exist-
ing functional condition. After the microphone is no longer
used, the functional condition shall be re-established.
e
Unless 13.3 applies, the microphone shall broadcast voice
messages to a pre-configured set of emergency loud-
speaker zones.
13.2 Microphone priority - Optional function
13.2.2 Where more than one microphone is configured at each
priority level, only one microphone shall be active at any one
time. If more than one microphone at the same priority is acti-
vated, the most recently activated microphone shall be
enabled.
13.3 Microphone emergency loudspeaker zone
control - Optional function
The s.s.c.i.e. may be configurable to route microphone mes-
sages to groups of emergency loudspeaker zones, with each
group containing at least one emergency loudspeaker zone.
Clause / Requirement
14 Design requirements
14.2 Documentation
14.2. 1 The manufacturer shall prepare installation and user doc-
umentation, which shall be submitted to the testing authority
together with the s.s.c.i.e. This shall comprise at least the fol-
lowing:
b
technical specifications of the inputs and outputs of the
s.s.c.i.e., sufficient to permit an assessment of the mechani-
cal, electrical, and software compatibility with other compo-
nents of the system (e.g. as described in
ISO 7240-1), including where relevant
3
the maximum number of alarm inputs from an emer-
gency detection system
c
installation information, including
1
the suitability for use in various environments,
2 how the requirements of 14.3.3 and 14.5.3 can be met if
the s.s.c.i.e. is contained in more than one cabinet,
3 how the requirements of 14.3.3 and 14.5.4 can be met if
the s.s.c.i.e is designed to be used with power-supply
equipment contained in a separate cabinet,
4
mounting instructions, and
5
instructions for connecting the inputs and outputs.
14.3.3 The s.s.c.i.e. may be housed in more than one cabinet. If
the documentation shows that the cabinets may be installed in
locations distributed within a site, then all of the mandatory
manual controls and indicators shall be on one cabinet or on
cabinets declared to be suitable only for mounting adjacent to
each other.
NOTE For the purposes of 14.3.3, adjacent cabinets are those
that are mounted in physical contact with each other.
14.8 Indications on alphanumeric displays
14.8.2 Alphanumeric displays used for mandatory indications
shall have at least one clearly distinguishable window, consist-
ing of at least two clearly identifiable fields.
14.8.3 If not included in the displayed information, the purpose
of each field shall be clearly labelled.
14.8.4 Where roman characters are used, a field shall be capa-
ble of containing at least the following:
a
at least 16 characters where the display of a functional con-
dition uses a cross-reference to other information to identify
the location;
b
at least 40 characters where the display is intended to
include the complete information on the location of a func-
tional condition.
14.8.5 Where other characters are used, a field shall be capa-
ble of containing at least the following:
Bosch Security Systems | 2011-02
Compliance
If the configured call of the emergency microphone was given a
higher priority than the calls that generate alert and evacuate
signals within the same emergency loudspeaker zone, these
calls will be aborted and mute.
Praesideo will resume overruled calls after the overruling call
has finished, providing that the overruled call was without live
speech and had emergency priority.
The emergency state that was entered upon starting a call with
emergency priority, will remain until explicitly manually reset.
Praesideo allows for free assignment of emergency loud-
speaker zones to calls that may contain live speech or prere-
corded messages.
This assignment can be manually during operation or in
advance during configuration.
Praesideo allows more than one microphone to be configured
for calls with the same priority, but in that case typically the
most recently activated one will not be enabled until the previ-
ous one has finished, i.e. first come, first served. Only in case of
the highest priority, 255, multiple calls with this priority act on
overruling basis, i.e. the most recently activated microphone
will be enabled.
Only one microphone will be active at any one time in the same
zone.
Praesideo allows for configuration of zone groups, containing
one or more emergency loudspeaker zones. Calls can be made
to a free selection of zones and zone groups.
Compliance
The inputs and outputs for audio and control are described in
the IUI, including the technical data, system functions, configu-
ration instructions, compliancy to standards. This includes the
information as requested in 14.2. 1 b 3.
The IUI contains all information as requested in 14.2. 1 c
1-5.
In case Praesideo is installed in multiple cabinets in locations
distributed within a site, the installer must arrange that all man-
datory manual controls and indicators are on the same location,
either by installing them on a single cabinet or on adjacent cab-
inets that are mounted in physical contact with each other.
The display of the network controller is used to display manda-
tory indications. It consists of two separate lines of text, each
representing a specific field, clearly identifiable.
Indication of the voice alarm condition is by means of the text
'Emergency' and the name of the key that activated the voice
alarm condition. Indication of the fault warning condition is by
means of the text 'Faults' and an indication of the number of
active faults in the system. Individual faults with details are
shown in a menu structure.
The display of the network controller consists of two lines with
16 characters each. It uses a menu with rotary knob navigation
to select additional detailed information about functional condi-
tions.
Not applicable, see 14.8.4.a.