Test procedure
• Tester must be within the detection coverage.
• Switch power on.
• KDP3 takes approx. 60sec to warm up with load and red LED on, then turns
off after warming up time.
• Walk from outside across to the detection pattern until red LED turns on for
approx. 2sec then off, the next trigger should be 2sec interval (See FIG.24).
• Adjusting lens shield for desired detection range.
Trouble shooting
Problem
Possible cause
Lighting
1.Power does not turn on.
device does
2.Wired incorrectly.
not turn on
3.Lux knob adjusted
incorrectly.
4.Malfunctioned load.
Lighting
1. Auto off time is set too
device does
long.
not turn off
2. Detector is nuisance
triggered.
3. Wired incorrectly.
LED does not
1. Time konb is not set to
turn on
Test.
2. Exceeding the detection
range.
www.grupotemper.com
KDP3 360
Presence detector
Suggested solution
1. Switch on the power.
2. Refer to wiring diagrams
for correct connection.
3. Check if Lux knob is set to
the correct position.
4. Replace the disabled load
with a new one.
1. Set auto off time to a
shorter time and check the
load is switched off or not
according to the pre-set off
time.
2. Keep away from detection
coverage to avoid activating
detector while doing the test.
3. Make sure load and wires
are connected correctly.
1. Time knob must be located
to Test position.
2. Walk in the effective
detection range of 8m
diameter.