KDP3 360
Presence detector
Case 2: Manual on switching (Lux settings is invalid):
If the lighting is under off mode, it can be manually switched on.
If the lighting is switched on manually by pressing ( 1sec) the push button
(activate the manual on mode), it keeps on while the detector is triggered
constantly, and it turns off when no movement detected and the switch off
delay time elapsed, and the detector backs to the last setting mode before
entering into manual on mode.
If the device is in the manual on mode, the second press on the push button
activates the manual off mode.
Max. 10pcs slave detectors can be connected in parallel to the "R/S"
terminal of the master detector KDP3 to expand detection range if detection
range of one KDP3 does not match the user's desire. Slave detector can
only be used to transfer detecting signal to master detector for expanding
the detection range, the connected loads will only act according to the pre-
set values of master detector.
ON / OFF delay function
According to the changeable ambient light level, detector can postpone
load's delay time of turning on and off to avoid load's unnecessarily
turning on or off due to rapid ambient light change:
Ambient light level changes from bright to dark: If the ambient light
level keeps be lower than the preset Lux value for 10sec, the light will be
automatically switched on after 10sec. (LED will be on 10sec for indication)
Ambient light level changes from dark to bright: If the ambient light level
continuously exceeds the switch off Lux value for 5min, there are different
reactions according to the time setting value.
Time setting ≥ 5min, the light will be automatically switched off after 5min.
Time setting < 5min, the light will be automatically switched off when the
set time reached if no movement is detected during the 5min. But if there is
movement detected within the 5min, the time will be reset upon detection
and until 5min later, the light is switched off.