Installation of grille/frame assembly
See fi g. 24 - 25.
Carefully unpack the assembly and check for damage sustained in
transit.
Attach the assembly to the unit by using the two hooks.
Tighten the four fi xing screws, connect the two electric connectors and
insert the cables through the special cable fi xing hook.
Maintenance
Cleaning and maintenance operations must be carried out by
specially trained personnel.
Before performing any service or maintenance operations, turn OFF
the main power switch.
To open the unit grille: (See fi g. 48).
Turn the two screws through 90° (1/4 turn).
Diagnostic
A green LED on the electronic board signals the diff erent conditions:
•
Intermittent fl ashing LED – Normal operating conditions.
•
Fixed LED – Float Alarm.
•
Quick fl ashing LED – Temperature probe failure.
Filter cleaning
Clean fi lters in accordance with the actual operating conditions and
times (approximately every 6 months).
•
The acrylic air fi lter is washable in water.
Electrostatic and active carbon fi lters (which can be used on the
unit) are not washable but must be replaced.
(See fi g. 49).
Extract the fi lter
(See fi g. 50).
First vacuum clean the fi lter, then wash under tap water and fi nally dry.
Replace the fi lter in the correct position.
Prolonged shutdown:
•
Before starting the air conditioner:
28
42 GW...B
Maintenance and owner's guide
Use the screws supplied to fi x the frame in position.
Ensure that the frame is not distorted by excessive tightening, that it is
aligned with the false ceiling and above all that there is a seal between
the air inlet and outlet.
In the drawing gasket " " prevents return air from mixing with the
supply air and gasket " " prevents the supply air from leaking into the
ceiling void.
On completion, the gap between the unit frame and the false ceiling
must not be more than 5 mm.
- clean or replace the unit air fi lters.
- check and clean the drain pan and the condensate discharge of the
unit
- check tightness of electric connections.
Additional maintenance
•
The electric panel is easily accessible by removing the cover panel.
The inspection or replacement of internal components such as: fan
motor, coil, condensate discharge pump, fl oat switch, electric heater
(if fi tted), involve the removal of the condensate drain pan.
Condensate drain pan removal
•
During the removal operation of the condensate drain pan protect
the fl oor with a plastic sheet under the unit.
•
Remove the frame-grille assembly by loosening the screws; drain the
condensate water contained in the drain pan into a bucket of at least
10 litres capacity, using the special drain with a rubber plug.
•
Remove the electrical panel cover and disconnect the electric
connections, connectors Cv, Cg, Cp and the yellow-green ground wire
(see drawing in "electrical connections" section). (See fi g. 51).
•
Remove the four fi xing screws on the side of the drain pan and
carefully remove the condensate drain pan.
Guide for the owner
When installation and tests are completed instruct the Owner on the
main operating modes of the air conditioner, such as:
•
Turning the unit ON and OFF.
•
Changing the operation modes.
•
Temperature selection.
Leave the installation manual with the owner for future use during
maintenance operations or for any other needs.