AFQm IP54
3.3.- STORAGE FOR LONG PERIODS
If the device is not installed after receipt, the following recommendations must be observed to keep
the device in a good state:
Keep the device in a dry atmosphere and at a temperature of between -20ºC and 50ºC.
Avoid exposure to direct sunlight.
Keep the device in its original packaging.
If the active filter is stored for a long time disconnected from the mains, a specific process must be
applied to restore the internal dielectric layers of the DC bus capacitors.
dations for starting the device, according to the length of its storage period.
Storage time
< 1 year
> 1 year
3.4.- INSTALLATION
The Cabinet-type AFQm IP54 models are free-standing cabinets with 4 bearing supports on the floor.
The mounting surface must be solid, support the device's weight and be level.
The cabinet must never be welded to the floor using arc welding, as this may destroy
the electronic components.
Instruction Manual
Table 5: Start-up process, according to storage time.
No special treatment required.
Connect the AFQm IP54 to the mains at least one hour be-
fore starting up the device. Power the device and leave it in
STOP mode
shows the recommen-
Table 5
Process