AFQm IP54
Filtering
Response time
Phase compensation
Power factor correction
Programming of priorities
Parallel connection
Efficiency (filter harmonic 5º/7º)
Efficiency (reactive)
Efficiency (filter harmonic 5º/7º)
Efficiency (reactive)
Quantity
Type
Quantity
Type
Internal modules.
(8)
Field bus
Communications protocol
Baud rate
Stop bits
Parity
Network protocol
Display
Environmental conditions
Operating temperature
Storage temperature
Relative humidity (with no condensation)
Maximum altitude
Protection degree
Overvoltage category
Pollution degree
Instruction Manual
Filter specifications
2 ... 50 harmonic (adjustable)
Up to 100 devices of different calibres
Connection of the transformers only in the Master device
AFQm-3WF-100R
(8)
97.2 %
98 %
AFQm-3WF-070C
(8)
97.5 %
97.8 %
Fuses: AFQm-xxx-100R
(8)
type BS88 100A, 500Vac, gG 80kA I
Fuses: AFQm-xxx-070C
(8)
type BS88/A4 63A, 660/690Vac, gG 80kA I
RS-485 Communications
Ethernet communications
TCP/IP, Modbus TCP
User interface
7" TFT colour touch screen
Web server and datalogger
Environmental features
Indoor conditioned IEC 60721-3-3
3000 m a.s.l. ( 2000 m a.s.l. without performance degradation)
AFQm-3WF-xxxx-690, AFQm-4WF-xxxx-550
AFQm-3WF-xxxx-690, AFQm-4WF-xxxx-550
< 100 μs
Adjustable
Adjustable
Adjustable
AFQm-4WF-100R
97.2 %
98 %
AFQm-4WF-070C
96.9 %
97.2 %
2 per phase
t 76.5kA
2
2 per phase
t 23kA
2
RS-485
Modbus RTU
9600 bps
1
none
-10ºC ... +50ºC
-20ºC... +55ºC
0 ... 95%
5000 m s.n.m.
IP54
OVC III 300V
OVC III 600V
2
(8)
(8)
s
2
s
2
167