Table 15 (Cont.): Warnings messages.
Alarm and event messages
Wait for the environmental conditions to meet the requirements. If the alarm continues, contact the
TAS.
Main frequency out of the limits
This alert may be associated with transients and noise in the power supply voltage, or with incorrect
mains frequency values. Check the configuration. Check the quality of the power supply voltage. If it
continues, contact the TAS.
Mains current below the programmed level.
Check the configuration.
Filter working at full load
No action is necessary.
The power factor value measured is less than 0.7, which might indicate a connection error in the
measuring transformers, where the voltage phases do not correspond to the current phases.
Confirm that the connections are correct.
The power value measured is negative (generated power), which might indicate that the transformers
have been connected inversely.
Confirm that the connections are correct.
Internal error.
Contact the Technical Assistance Service.
This is a fault in one or more slaves.
The device does not stop and adjusts its operation to the number of available slaves. Check the status
of each internal module through its screen.
Mains frequency limits
Minimum current
Maximum load
Low power factor
Reverse power
Wxxx
Parallel filter in alarm
AFQm IP54
Instruction Manual