5.- START-UP
When the device has been powered the screen in
Before starting the active filter, it is necessary to follow the steps below:
1.- Go into the configuration screens,
tion.(See
"7 - CONFIGURATION"
Device "single" or "master"
2.-
(
shows the voltage and current (
Make sure the voltage measurements correspond to the real voltages of the installation.
Make sure the load current measurements correspond to the current levels of the installa-
tion.
3.- (Device "single" or "master") Go into the numeric values screens,
shows the load parameters (
Make sure the active power measurement of the load corresponds to the active power levels
of the installation.
Make sure the reactive power measurement of the load corresponds to the reactive power
levels of the installation.
Check the cos ɸ in the three phases. If phases appear with very high reactive power and very
low active power levels, this may indicate an error in the phase order. In this case, check the
power supply and current input connections.
4.- (Device "single" or "master") Go back to the home screen of the device,
no problem with the connections, the upper area should show the message "Stop".
If there is a problem with the filter connections or the configuration, the "Waiting for conditions"
message appears.
5.- (Device "single" or "master") Press the
the screen will show the message "Run".
122
Figure 27
Figure 27: Home screen.
and set up the device as required for the existing installa-
).
Go into the numeric values screens,
)
"6.2.5 - VOLTAGE / CURRENT / FREQUENCY")
"6.2.7 - POWER AND COS ɸ OF LOAD"
key to start the active filter. If it has started correctly,
appear on the display.
, and on the screen that
:
, and on the screen that
):
,
Figure 27
AFQm IP54
, if there is
Instruction Manual