AFQm IP54
shows the messages that could appear on the device.
Table 14
If the cause of the alarm disappears, the device will be reconnected automatically.
If the same alarm is triggered 5 times during a 1-hour period, the automatic device reconnection
function will be disabled.
The
key rearms the device if the cause of the alarm has disappeared or has been resolved.
If the device remains in a permanent alarm state, the screen shown in
If the display has entered energy saving mode, it is automatically disabled. The alarm screen disap-
pears when the display is touched.
Description
The AFQm IP54 current is too high.
Corrective
This alarm may be associated with transients and noise in the power supply voltage. Check the quality
action
of the power supply voltage. If it continues, contact the TAS.
Description
The mains voltage is too high.
This alarm may be associated with transients and noise in the power supply voltage, or with incorrect
Corrective
mains voltage values. Check the configuration. Check the quality of the power supply voltage. If it
action
continues, contact the TAS.
Description
The temperature of the power module is very high.
Corrective
Check that the fans are working. Clean or replace them if necessary. If it continues, contact the TAS.
action
Description
The temperature of the inductors is very high.
Corrective
Check that the fans are working. Clean or replace the fans if necessary. If it continues, contact the TAS.
action
Description
Detection of a potential resonance with a load
Corrective
The resonance detection function can be activated erroneously in installations with a very high volt-
action
age THD. Contact the TAS.
Instruction Manual
Figure 50: Permanent alarms.
Table 14: Alarm messages.
Alarm messages
Overcurrent L1/L2/L3
Mains overvoltage L1/L2/L3
High temp IGBT
High temp Inductor
Resonance
, is displayed.
Figure 50