Wilo Stratos MAXO Serie Instrucciones De Instalación Y Funcionamiento página 195

Ocultar thumbs Ver también para Stratos MAXO Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 442
10.6
Application and function of the
Wilo Net interface
Installation and operating instructions Wilo-Stratos MAXO/-D/-Z
Communication interfaces: Setting and function
NOTICE
If the signal type PT1000 was selected, it is possible to set a temperature correction
value for the measured temperature. With this the electrical resistance of a long
sensor cable can be compensated.
In the
"Settings" menu, select
1.
"External interfaces"
2.
"Analogue input (AI1) function" or "Analogue input (AI2) function"
3.
"Temperature correction" and set correction value (offset).
NOTICE
Optionally specify the position of the sensor for better understanding of the con-
nected sensor's function.
This configured position does not influence the function or sensor use.
In the
"Settings" menu, select
1.
"External interfaces"
2.
"Analogue input (AI1) function" or "Analogue input (AI2) function"
3.
"Select the sensor position".
The following positions are available:
▪ Internal sensor
▪ Analogue input 1
▪ Analogue input 2
▪ BMS
▪ Feed
▪ Return
▪ Primary circuit 1
▪ Primary circuit 2
▪ Secondary circuit 1
▪ Secondary circuit 2
▪ Accumulator
▪ Hall
▪ Circulation
Wilo Net is a bus system which enables up to eleven Wilo products to communicate
with one another.
Application for:
▪ Double pumps consisting of two single pumps
▪ Multi-pump system
▪ Gateway
▪ Remote control
Bus topology:
The bus topology consists of multiple stations (pumps), which are switched on in se-
quence. The stations (pumps) are connected via a shared line.
The bus must be terminated at both ends of the cable. This is done for the two external
pumps in the pump menu. All other subscribers should not have activated termination.
All bus subscribers must be assigned an individual address (Wilo Net ID). This address is
set in the pump menu of the respective pump.
To terminate the pumps:
In the
"Settings" menu, select
1.
"External interfaces"
2.
"Wilo Net setting"
en
195
Tabla de contenido
loading

Este manual también es adecuado para:

Stratos maxo-d 32/0,5-12Stratos maxo-z 32/0,5-12

Tabla de contenido