Important Notice; If You Have A Question - Best Power Fortress 750 Guia Del Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

The UPS ground (earth) conductor carries leakage current from the loads in addition to any
leakage current generated by the UPS. This UPS generates no more than 0.5 mA of current
(U model), or 1 mA of current (E model). To limit the total leakage current to 3.5 mA, the load
leakage must be limited to 3 mA on the U model and 2.5 mA on the E model. If you do not
know the load leakage current, replace the UPS power cord with a power cord that uses a locking
plug with a minimum rating of 10 A (such as IEC 309). If you do not have a matching
receptacle, consult an electrician to install the proper receptacle. The three-wire receptacle that
you plug the UPS into must have a good (low-impedance) ground (protective earth) connection
to provide a safe path for leakage current.

If You Have a Question

If you have a question or problem, please go to IBM Service Support. If you need to contact
the manufacturer (Best Power) directly, see the list of Best Power offices. You can also get more
product information by visiting Best Power's World Wide Web site at
http://www.bestpower.com/as400.
SAVE THESE INSTRUCTIONS! THIS MANUAL CONTAINS IMPORTANT
INSTRUCTIONS FOR YOUR UPS.
The installation and use of this product must comply with all national, federal, state, municipal,
or local codes that apply. If you need help, please follow the Customer Process for Service in
IBM Service Support.
ENGLISH

Important Notice

2
Tabla de contenido
loading

Este manual también es adecuado para:

Fortress 1050Fortress 1425Fortress 1800Fortress 2250

Tabla de contenido