Gas System Connection; How To Achieve The Nominal Thermal Capacity; Pressure Check; Adjusting The Minimum Thermal Capacity - Diamond OMNIA Serie Manual De Instrucciones

Plancha calefaccion gas
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

2.6

GAS SYSTEM CONNECTION

- The unit should be supplied with gas having the characteristics and the pressure shown on Table II.
- The gas pressure is measured at the initial pressure outlet with the burner on (see Fig. 1).
- The unit is tested and fitted to operate with natural gas H G20 - 20mbar.
* N.B. Should the supply pressure vary more than +10% of the nominal pressure, it is advisable to install a pressure
regulator ahead of the unit to guarantee the nominal pressure.
- Gas supply connection should be performed by means of metal piping of an appropriate cross section and an approved
shutoff cock should be fitted at source.
- Having connected the gas supply, you should make sure no leaks exist at the joints by checking with bubble soap.
DISCHARGE OF EXHAUST FLUE PRODUCTS VIA A DRAFT HOOD.
TYPE "A
" UNIT.
1
The gas unit should be placed beneath a draft hood with its system complying with the Regulations. (This unit needs at least
2cu.m/hr l kW T.C. (Thermal Capacity). Check kitchen ventilation: it should by complying with the Regulations in force.
2.6.1

HOW TO ACHIEVE THE NOMINAL THERMAL CAPACITY

Check whether the unit is fitted for the gas type, pressure and category corresponding with the main gas supply.
Indication shown on packing and/or the label of the unit.
If the unit is fitted for another gas type or pressure, you need to first effect a change over to the other gas type.
See Table II for the nozzle, the idle screw (bypass), the primary air regulation, (X mm), the pilot nozzle and the nozzle pressure
for the main burner.
N.B.: The names of nozzles "2H" and "3+" are shown on the left side of Table II.
2H= G20 - 20mbar
3+= G30 29mbar and/or G31 - 37mbar coupled gas and pressure.
In our sector, we almost always have to deal with G31 - 37mbar!
Table II shows the types of gas and pressure for all burners and respective nozzles, the X mm distance for the adjustment of
primary air (see Fig. 3), the idle screw (bypass), the pilot nozzle, the maximum and minimum pressure at nozzle, the maximum
and minimum thermal capacity, and the gas consumption in l/hr (15°C) or in g/hr in the case of L.P.G.
Attention: If the incoming gas' "dynamic" pressure to the unit is lower than the minimum pressure on Table II, connection
is prohibited; furthermore, the fitter should notify the gas Company that the supply pressure is too low.
N.B.: Should the pressure vary more to than +10% of the nominal pressure, e.g. for G20 ž 22mbar, it is advisable to mount
a pressure regulator ahead of the unit in order to guarantee the nominal pressure.
Should the supply pressure exceed the maximum pressure on Table II, e.g. for G20 ž 25mbar, notify the gas Company.
Make sure the inlet and nozzle pressures agrees with the values shown on Table II.
2.6.2

PRESSURE CHECK

INCOMING PRESSURE CHECK (Pe) Fig. 1
Pressure is measured with a manometer 0 ÷ 80mbar (precision at least 0.1mbar).
The pressure socket Fig. 1 is located on the G 1/2" gas ramp behind the panel; undo the screw (A) of the pressure socket (B),
attach the silicone rubber to the manometer, ignite the burner (Fig. 3 position 4) and take the incoming "dynamic" pressure.
Fasten the screw (A) back with a gas washer (C), check gas sealing with bubble soap.
NOZZLE PRESSURE CHECK (Pi) Fig. 2.
The pressure socket is located above the nozzle holder (Fig. 2).
The silicone rubber is prepared for high temperatures and should be protected with tin foil to avoid its burning.
2.6.3

ADJUSTING THE MINIMUM THERMAL CAPACITY

The right minimum for thermal capacity is achieved by means of the "calibrated" bypass idle screw firmly tightened in ac-
cordance with Table II.
Ignite the burner according to Chapter 6 "Instructions to Users" in the maximum position (8); after approx. 15 minutes of
pre-heating, turn knob to the minimum position (1).
For the 2nd and 3rd Family, the bypass idle screw should be all screwed down.
2.6.4

LIQUID GAS OPERATION CONTROL

Check whether the fitted nozzles comply with the indications on Table II.
Check whether the incoming pressure complies with the indications on Table II.
Make sure that the L.P.G. gas system has two pressure regulators of suitable capacity and that the evaporation capacity is
sufficient. See also the publication "Installation Regulations and Characteristics of L.P.G. Systems".
GB
- 14 -
Tabla de contenido
loading

Tabla de contenido