DIESEL IGNITION AND REGULATION

Turn the switch on the control panel to the "O" position (open).
Turn the switch "fuel change-over" to the "OIL" position.
Close the auxiliary air to the head unscrewing the pawl (A)
and pulling the rod (B) down to its end of stroke. Retighten the
pawl (A).
Close the gate and open the shut-off elements.
Check that there is water in the boiler and that the gates on the
system are open.
Make sure that the products of combustion can be released
freely (boiler and chimney dampers open).
Check that the voltage of the electric line the equipment must
be connected to, complies with the manufacturer prescriptions,
and that the motor electric connections are properly set for the
available voltage. Also check that all electric connections made
on-site are performed correctly as shown in our wiring diagram.
Start the fuel supply auxiliary circuit and check for its correct
operation, then set pressure to nearly 0,5÷3 bar if such circuit
features a pressure regulator.
Remove the vacuum gauge connection plug from the pump and
open the gate on the fuel pipe. Wait for the fuel to flow out of the
hole without air bubbles and close the gate. In case no supply
circuit under pressure is available, fill the pump by pouring fuel
into the supply hose.
Fit a pressure gauge (full scale approx. 4 bar) to the pump
vacuum gauge connection point to check the pressure value at
which the fuel reaches burner pump. Fuel pressure must remain
within 0,5÷3 bar also when the burner is off.
Open the gates placed on the diesel pipes.
Power the electric line to which the burner is connected. Manually
press the specific remote control switches to check that the fan
and pump motors turn in the correct direction. If necessary,
change the position of the two cables of the main line to reverse
the rotation direction.
Start the burner pump by manually pressing the relevant remote
control switch until the pump pressure gauge detects a slight
pressure. A slight pressure in the circuit indicates that it has
been filled up.
Connect (pos. I) the switch (1) on the control panel to power
the equipment and close the thermostat line turning the selector
(2) in the "closed" position. If thermostats or pressure switches
(safety and boiler) are closed as well, the operating cycle will
start. The equipment turns on. For the regulation of the burner,
see la "RAPID GUIDE TO PROGRAMMING" and the specific
instruction manual for the "BT 340" electronic cam .
Check that the flame detector is triggered.
FLAME SENSOR
If the flame is detected by the UV photocell remember what
specified below. A slight amount of grease will strongly
compromise the passage of the light radiations, preventing the
internal sensitive element from receiving the quantity of radiations
required for proper operation. If the bulb is fouled, it must be
properly cleaned. Even the simple contact with your fingers can
leave a slight amount of grease that is enough to compromise the
A
Rod position with "CLOSED" auxiliary air to the nozzle
(DIESEL operating mode)