Instructions
vacuum tube or air nozzle.
If the refrigerant system has been opened, the
system has to be flushed with dry air or nitrogen
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to be
done, it shall be done in such a way that no refri-
gerant can escape to the environment.
Service
panel
removal
W09 Version.
OP-LSQM014, 018, OP-MSGM018, 021, OP-
MSYM009, 012, 014, OP-MSGM012, 015
OP-MSYM018, OP-LSQM026 - 034 - 048 - 068
- 074, OP-MSBM018 - 024 - 026 - 034, OP-
MSXM034 - 044 - 046 - 057, OP-MSGM026 -
033, OP-LSQM067 - 084 - 098, OP-MSXM068
- 080 - 093 - 099 - 108
16 - Fan speed controller setting for R134a/R513A
refrigerant
Fan speed Controller
FSC type
Spare part number
061H3144
XGE-2C
17 - Pressostat factory settings
Refrigerants
R404A/R507/R407A/R407F/R448A/R449A/R452A
R134a/R513A
4 | AN23308644013404-001201
Step 1: Pull the cap from the isolator switch
using screw driver.
Step 2: Unscrew the isolator switch from the ser-
vice panel.
Step 3: Take out the isolator switch.
Step 4: Removing the service panel.
13 – Declaration of conformity
procedure
for
• Pressure Equipment Directive 2014/68/EU
EN 378-2:2016 - Refrigerating systems and
Heat Pumps - Safety and environmental requi-
rements-Parts 2: Design, construction, testing,
marking and documentation
Low Voltage Directive 2014/35/EU EN 60335-
1:2012 + A11:2014- Household and similar elec-
trical appliances-Safety-Part 1: General requi-
rements-for all above mentioned condensing
units
Eco-design DIRECTIVE 2009/125/ EC, esta-
blishing a framework for the setting of Eco-de-
sign requirements for energy-related products.
REGULATION (EU) 2015/1095, implementing
Eco-design Directive 2009/125/EC with regard
to Eco-design requirements for professional
refrigerated storage cabinets, blast cabinets,
condensing units and process Chiller.
• Condensing unit measurements are made
according to standard "EN 13771-2:2007" – Com-
pressor and condensing units for refrigeration-
performance testing and test methods- part 2:
Condensing units
14 - Warranty
Always transmit the model number and serial num-
ber with any claim filed regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
Refrigerant
letter
Q
H
R404A/R507/R134a/R513A/ R407A/
X
R407F/R448A/R449A/R452A
Y
B
R404A/R507/R449A/R452A
G
X
If refrigerant used is R134a or R513A
For Refrigerant
R404A/R452A/R507
R404A/R507
R404A/R507/R449A
R134a/R513A
High pressure settings (bar (g))
ON
OFF
23
27
13
17
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or main-
tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmit-
ted with the warranty claim.
15 – Disposal
Danfoss recommends that condensing
units and oil should be recycled by a
suitable company at its site.
Factory
Action required
setting
15 bar
15 bar
360°=1 turn = Approx 0.8 bar
(Clockwise rotation =
15 bar
Increase pressure setting,
Counter clockwise rotation =
15 bar
Decrease pressure setting)
15 bar
8 bar
Rotate the screw by 9 turns in counter
15 bar
clockwise direction to reach 8 bar
Low pressure settings (bar (g))
ON
2
2
© Danfoss | DCS (CC) | 2019.01
OFF
1
1