Instructions
Optyma™ Slim Pack
OP-LSQM / LSHM / MSXM / MSHM /
MSGM / MSYM / MSBM
Name plate
A
OP-MSXM034MLW05E
B
114X7062
C
Application
MBP
D
Refrigerant
(1) R404A, R452A, R507,
R448/9A
M.W.P. HP
(1) 28 bar
E
LP
(1) 7 bar
F
Voltage
380-400V~3N~50Hz
LRA
30,5 A
OIL INSIDE POE 46
G
Serial No.
123456CG4818
Barcode Serial No:
EAN No.
XXXXXXXXXXXXX
Danfoss A/S, 6430 Nordborg, Denmark
A: Model
B: Code number
C: Application, Protection
D: Refrigerant
E: Housing Service Pressure (Maximum working
pressure)
F: Supply voltage, Locked Rotor Ampere,
Maximum Continuous Current
G: Serial Number and bar code
Picture 2
1 – Introduction
These instructions pertain to Optyma
Pack condensing units OP-LSHM/MSHM/MSGM/
LSQM/MSXM/MSYM/MSBM
(R448A,
R452A, R407A, R407F, R507, R404A, R134a,
R513A) used for refrigeration systems. They pro-
vide necessary information regarding safety and
proper usage of this product.
The condensing unit includes following:
• Scroll/reciprocating compressor
• Microchannel heat exchanger
• Dual pressure switches
• Service valves Suction/ liquid
• Weather proof housing
• Filter drier
• Cranckcase heater for compressor
• Receiver with stop valve
• Sight glass
• Phase sequence relay (scroll compressors)
• Fully pre-wired electrical panel (including main
switch, compressors contactor, overload relay)
• Fan speed controller and External main switch
(W09 only)
2 – Handling and storage
• It is recommended not to open the packaging
2 | AN23308644013404-001201
MADE IN INDIA
IP54
(2) R134a
N
(2) R513A
(2) 23 bar
(2) 5 bar
MCC
7,5 A
Picture 1 : Minimum mounting distances
L
[mm]
[mm]
250
650
before the unit is at the final place for installation.
Slim
• Handle the unit with care. The packaging al-
TM
lows for the use of a forklift or pallet jack. Use
R449A,
appropriate and safe lifting equipment.
• Store and transport the unit in an upright position.
• Store the unit between -35°C and 50°C.
• Don't expose the packaging to rain or corrosive
atmosphere.
• After unpacking, check that the unit is com-
plete and undamaged.
3 – Installation precautions
Do not braze as long the condensing unit is
under pressure.
Never place the unit in a flammable atmosphere
Place the unit in such a way that it is not blocking
or hindering walking areas, doors, windows or similar.
• Ensure adequate space around the unit for air
circulation and to open doors. Refer to picture1
for minimal values of distance to walls.
• Avoid installing the unit in locations which are daily
exposed to direct sunshine for longer periods.
• Avoid installing the unit in aggressive and dus-
ty environments.
• Ensure a foundation with horizontal surface
(less than 3° slope), strong and stable enough
L
O
M
M
N
O
[mm]
[mm]
550
550
Picture 3
Schrader valve
Mounting bolts (not supplied)
Installation and servicing of the conden-
sing units by qualified personnel only. Follow
these instructions and sound refrigeration
engineering practice relating to installation,
commissioning, maintenance and service.
The condensing unit must only be used for
its designed purpose(s) and within its scope of
application.
Under all circumstances, the EN378 (or
other applicable local safety regulation)
requirements must be fulfilled.
The condensing unit is delivered under nitro-
gen gas pressure (1 bar) and hence it cannot
be connected as it is; refer to the «installation»
section for further details.
The condensing unit must be handled with cau-
tion in the vertical position (maximum offset
from the vertical : 15°)
Anticlockwise (open)
Clockwise (Close)
to carry the entire unit weight and to eliminate
vibrations and interference.
• The unit ambient temperature may not exceed
50°C during off-cycle.
• Ensure that the power supply corresponds to
the unit characteristics (see nameplate).
• When installing units for HFC or HFO refrige-
rants, use equipment specifically reserved for
HFC or HFO refrigerants which was never used
for CFC or HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The suction piping connected to the compres-
sor must be flexible in 3 dimensions to dampen
vibrations. Furthermore piping has to be done
in such a way that oil return for the compres-
sor is ensured and the risk of liquid slug over in
compressor is eliminated.
4 – Installation
• The installation in which the condensing unit is
installed must comply to EEC Pressure directive
(PED) no. 97/23/EC. The condensing unit itself
is not a "unit" in the scope this directive.
• The unit must be securely installed on a stable
© Danfoss | DCS (CC) | 2019.01